BLD15-02982
| FIRE-Final Inspection | 6/2/2016 | 6/2/2016 | 6/2/2016 2:10:26 PM | P | FAIL |
|
|
Exit sign was inoperable at time of inspection, power is isolated to tenant space so emergency power supply was depleted. No addressing seen for this tenant space, address number for this space needs to be installed, 4 in tall numbers with 1/2 inch brush stroke. No fire extinguisher in tenant space, fire extinguisher needs to be installed. Main entry door has thumbturn deadbolt installed on door, thumbturn deadbolt needs to be removed and a double-keyed deadbolt needs to be installed.
|
FIR16-00172
| INSP-Final Inspection | 6/1/2016 | 6/2/2016 | 6/2/2016 1:43:43 PM | P | PASS |
|
|
Final fire alarm inspection passed/complete
|
BLD16-01925
| FIRE-Final Inspection | 6/1/2016 | 6/2/2016 | 6/2/2016 12:56:46 PM | A | PASS |
|
|
No fire sprinklers, no fire alarms, fire extinguisher is in place with current inspection tag. Final life fire safety inspection passed/complete.
|
FIR15-00747
| INSP-Final Inspection | 6/2/2016 | 6/2/2016 | 6/2/2016 11:57:06 AM | A | PART |
|
|
Inspected pull stations, smoke detectors and A/V's in office area's, battery room, electrical room and fire sprinkler riser room, all tested correctly. Inspected tamper switches, flow switches and low air alarm. Outside bell did not ring with dry system water flow or south side wet system water flow, items will be corrected and reinspected at next inspection request.
|
BLD15-04191
| FIRE-Final Inspection | 6/1/2016 | 6/2/2016 | 6/2/2016 10:42:13 AM | A | PART |
|
|
Fire sprinklers complete for level 4, fire alarm complete for level 4, final life fire safety for level 4 complete. Level 3 will be reinspected at later date for fire extinguishers and egress lighting on south side of floor (remaining egress lighting for level 3 tested and passed) Fire sprinklers complete for level 3, alarms will be retested for A/V devices that were disconnected during this inspection.
|
FIR16-00097
| INSP-Alarm Testing | 6/1/2016 | 6/2/2016 | 6/2/2016 10:38:43 AM | A | DONE |
|
|
Alarm inspection/testing for level 4 complete, contractor had some A/V devices on 3rd floor disconnected (northeast corner class room, total of 4 A/V's), will need to perform inspection for disconnected devices when level 2 is inspected.
|
FIR16-00102
| INSP-Final Inspection | 6/1/2016 | 6/2/2016 | 6/2/2016 10:35:28 AM | A | PASS |
|
|
Final fire sprinkler inspection for level 3 passed/complete.
|
FIR16-00092
| INSP-Final Inspection | 6/1/2016 | 6/2/2016 | 6/2/2016 10:34:47 AM | A | PASS |
|
|
Final fire sprinkler inspection for level 4 passed/complete.
|