Inspections for the day of: Thursday, June 2, 2016.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD15-02982 FIRE-Final Inspection6/2/20166/2/20166/2/2016 2:10:26 PMPFAIL
Exit sign was inoperable at time of inspection, power is isolated to tenant space so emergency power supply was depleted. No addressing seen for this tenant space, address number for this space needs to be installed, 4 in tall numbers with 1/2 inch brush stroke. No fire extinguisher in tenant space, fire extinguisher needs to be installed. Main entry door has thumbturn deadbolt installed on door, thumbturn deadbolt needs to be removed and a double-keyed deadbolt needs to be installed.
FIR16-00172 INSP-Final Inspection6/1/20166/2/20166/2/2016 1:43:43 PMPPASS
Final fire alarm inspection passed/complete
BLD16-01925 FIRE-Final Inspection6/1/20166/2/20166/2/2016 12:56:46 PMAPASS
No fire sprinklers, no fire alarms, fire extinguisher is in place with current inspection tag. Final life fire safety inspection passed/complete.
FIR15-00747 INSP-Final Inspection6/2/20166/2/20166/2/2016 11:57:06 AMAPART
Inspected pull stations, smoke detectors and A/V's in office area's, battery room, electrical room and fire sprinkler riser room, all tested correctly. Inspected tamper switches, flow switches and low air alarm. Outside bell did not ring with dry system water flow or south side wet system water flow, items will be corrected and reinspected at next inspection request.
BLD15-04191 FIRE-Final Inspection6/1/20166/2/20166/2/2016 10:42:13 AMAPART
Fire sprinklers complete for level 4, fire alarm complete for level 4, final life fire safety for level 4 complete. Level 3 will be reinspected at later date for fire extinguishers and egress lighting on south side of floor (remaining egress lighting for level 3 tested and passed) Fire sprinklers complete for level 3, alarms will be retested for A/V devices that were disconnected during this inspection.
FIR16-00097 INSP-Alarm Testing6/1/20166/2/20166/2/2016 10:38:43 AMADONE
Alarm inspection/testing for level 4 complete, contractor had some A/V devices on 3rd floor disconnected (northeast corner class room, total of 4 A/V's), will need to perform inspection for disconnected devices when level 2 is inspected.
FIR16-00102 INSP-Final Inspection6/1/20166/2/20166/2/2016 10:35:28 AMAPASS
Final fire sprinkler inspection for level 3 passed/complete.
FIR16-00092 INSP-Final Inspection6/1/20166/2/20166/2/2016 10:34:47 AMAPASS
Final fire sprinkler inspection for level 4 passed/complete.