Inspections for the day of: Friday, June 2, 2017.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE16-04020 Final5/31/20176/2/20176/2/2017 2:11:00 PMPPASS
Inspection on the two beds/hall in basement. Homeowners numbers for access.
Jen-###-####
Rich-###-#### Phone #: ###-#### Inspection requested via web by Greg Traudt
Basement rough in not noted. Contractor stated inspector 363 had been scheduled shortly after permanent service inspection. All tested out OK. Final ok
ELE16-03736 Final6/2/20176/2/20176/2/2017 1:34:36 PMPFAIL
Side door is still unlocked. Call ###-#### ahead of time and I can meet you there if needed. Phone #: ###-#### Inspection requested via web by Brannon Brown
BCC 4-05-32 Code violations not to be retained. 440.6 AC overcurrent protection shall be based on name plate rating. 25 amp max 30 amp installed.
210.8- Receptacle located in kitchen area for cabinet with sink in front of island shall have GFCI protection.
406.4(D)- Replacement receptacles if grounding type shall have GFCI protection.
408.4- Circuit directory shall be labeled accurately.
422.31(D)- A disconnecting means shall be provided for appliances rated over 300 VA. Oven, water heater. Lock-out acceptable.
ELE17-01219 Final6/2/20176/2/20176/2/2017 12:21:49 PMAPASS
Please call Gabe (###-####) 30 minutes ahead for access Phone #: ###-#### Inspection requested via web by Brad Girard Final ok
ELE17-01650 Rough-In Permanent Service6/2/20176/2/20176/2/2017 11:39:06 AMAFAIL
Phone #: ###-#### Inspection requested via web by Greg Traudt
110.3- Furnace junction box cover removed. Reinstall box as provided by manufacture.
250.148- In boxes with more than 1 circuit all equipment grounding conductors shall be bonded together in that box.
300.4- NM cable shall be protected from physical damage where run thru bored holes that do not maintain 1 1/4" from framing surface.
314.25- Kitchen can has junction box cover not completely covering opening.
334.15- Wher NM cable is installed on stairway it is subject to damage when drywall is being installed. Relocate.
408.7- Unused breaker space in basement panel shall be sealed.
Garage has only 2 circuits, if more than 2 grounding electode connection required.
ELE17-00699 Final6/1/20176/2/20176/2/2017 10:41:30 AMAFAIL
Phone #: ###-#### Inspection requested via web by Shaun Kirkman
110.3- Master bath floor heat- installation not complete. As per manufacturers instructions floor cover and base shall be complete.
BCC 4-05-15- It shall be unlawful for any person to perform electrical work with out contractors license. Finish carpenter removed island box during inspection.
Warning given.
Re-inspection fee assessed
ELE17-01645 Rough-In Permanent Service6/1/20176/2/20176/2/2017 10:27:29 AMAPASS
Phone #: ###-#### Inspection requested via web by Lynn Cable
Rough in ok cover p/s u/g n ok
ELE17-00564 Final6/1/20176/2/20176/2/2017 9:33:09 AMANH
Kevin-call for access Phone #: ###-####
Called, left message, waited 5 minutes for return call. Must recall
ELE17-01500 Electrical Rough-In6/1/20176/2/20176/1/2017 1:21:57 PMAPASS
Cover Phone #: ###-#### Inspection requested via web by Louis Keller
Check interior panel for seperation of grounds and neutrals. Most wiring to be surface mounted for industrial look.
Walls and hardlid rough in ok cover