Inspections for the day of: Friday, June 2, 2017.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR16-00724 INSP-Final Inspection5/31/20176/2/20176/2/2017 3:19:11 PMPFAIL
West roof top HVAC unit would not start up to test unit shutdown upon induct smoke detector activation. Fire alarm control panel signage needs to be installed on exterior door leading to the fire panel. All other associated fire alarm components tested satisfactorily.
FIR16-00705 INSP-Final Inspection5/31/20176/2/20176/2/2017 3:15:23 PMPFAIL
Fire sprinkler head is to far off of wall, east space near fire sprinkler riser room wall. Heads are still masked from painters in east section of building by seperating wall. Signage needs to be installed on valves/riser trim in fire pump/fire riser room. PODS section office area shows walls going all the way to the deck as shown on fire sprinkler city approved drawings as well as BLD permit city approved drawings, walls do not go all of the way up, fire sprinklers will need to be added or walls will need to go all of the way up to roof deck Fire bell signage needs to be installed on exterior bell. Fire sprinkler riser room signage needs to be installed on exterior door for fire riser/fire pump room.
BLD17-00849 FIRE-Final Inspection6/1/20176/2/20176/2/2017 2:48:03 PMPFAIL
Fire life safety cannot be completed for this permit until the fire sprinkler/fire alarm (FIR16-00724 for fire alarm and FIR16-00705 for fire sprinkler) permits for core and shell are complete as well as the BLD (BLD16-02176) permit for core and shell is complete. After core and shell permits are passed then the FIR permit (FIR17-00190) for fire sprinklers associated with this project will need to be completed before life fire safey inspection can be performed.
FIR16-00596 INSP-Final Inspection5/31/20176/2/20176/2/2017 2:10:50 PMPPASS
Final inspection for underground supply passed/complete
FIR16-00512 INSP-Final Inspection6/1/20176/2/20176/2/2017 9:16:32 AMPPASS
Final fire sprinkler inspection passed/complete
FIR17-00175 INSP-Final Inspection6/1/20176/2/20176/2/2017 9:15:57 AMAPASS
Final fire alarm inspection passed/complete
FIR16-00664 INSP-Final Inspection6/1/20176/2/20176/2/2017 8:22:55 AMAPASS
Final fire sprinkler inspection passed/complete