ELE20-01863
| Electrical Rough-In | 6/2/2020 | 6/2/2020 | 6/2/2020 3:46:18 PM | P | FAIL |
|
|
building vacant. call for key code. Phone #: ###-#### Inspection requested via web by David McClellan BCC- A city approved set of prints shall be on site prior to an inspection. 330.30- MC support and secure on east wall has been taken apart to add studs. Wiring hanging, boxes not secured, mudrings removed. General contractor trying to repair illegally. 517.13- Exam and treatment areas shall have an effective grounding path as per 250.118.
|
ELE20-01869
| Electrical Rough-In | 6/2/2020 | 6/2/2020 | 6/2/2020 3:02:28 PM | P | PASS |
|
|
5433. Lockbox in hallway on fire extinguisher box Phone #: ###-#### Inspection requested via web by Dean Gernaat City approved set of print on site. Conference room shall comply with 210.71. 375 square foot room will require 2 floor receptacles and 7 minimum total receptacles. Wall rough in ok cover.
|
ELE20-00389
| Final | 6/2/2020 | 6/2/2020 | 6/2/2020 2:07:25 PM | P | PASS |
|
|
Thank you Phone #: ###-#### Inspection requested via web by Eric Brown Final ok
|
ELE20-01769
| Temporary Service | 6/2/2020 | 6/2/2020 | 6/2/2020 1:24:03 PM | P | FAIL |
|
|
Contact: Damonn Barr Phone #: ###-#### Inspection requested via web by Deb Gooden 550.4- Mobile job trailers shall comply with article 550 for power supply. 550.32- Service equipment shall be located adjacent to unit it serves and not be located in or on unit.
|
ELE19-03913
| Final | 6/2/2020 | 6/2/2020 | 6/2/2020 12:48:54 PM | P | PASS |
|
|
Install EMC sign above Jump parking garge enterance on 11th street. All Primary Power by others Phone #: ###-#### Inspection requested via web by Ken Olsen Final ok
|
ELE19-00601
| Electrical Rough-In | 6/1/2020 | 6/2/2020 | 6/2/2020 10:50:28 AM | A | PASS |
|
|
6th floor guest rooms cover. Danny is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen 602 thru 624 baths, HVAC, hardlids rough in ok cover
|
ELE20-01395
| Rough-In Permanent Service | 6/1/2020 | 6/2/2020 | 6/2/2020 9:37:24 AM | A | PASS |
|
|
It will be open. If you have any questions please feel free to contact ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clayton Morgan Rough in ok cover p/s o/h n ok
|
ELE20-01393
| Rough-In Permanent Service | 6/1/2020 | 6/2/2020 | 6/2/2020 9:36:10 AM | A | PASS |
|
|
It will be open. If you have any questions please feel free to contact ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clayton Morgan Rough in ok cover p/s o/h n ok
|