Inspections for the day of: Tuesday, June 20, 2000.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorMarv Burrus
TitleELE
Phone #340-1297
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE00-02301 Final6/19/20006/20/20006/20/2000 12:00:00 AMAPASS
KANDOR STE B\\###-#### Re-located light switches and fixtures. Completed 6/21/00 11:54:45 AM
ELE00-01938 Rough-In Permanent Service6/19/20006/20/20006/20/2000 12:00:00 AMAFAIL
Scheduled by a contractor via Hello! on 06/19/2000 at 12:09:40. Contact: ###-####. Ground-choke for EMT raceway for grounding conductor required. 6/21/00 11:56:16 AM
ELE00-01367 Electrical Rough-In6/19/20006/20/20006/20/2000 12:00:00 AMAPART
Scheduled by a contractor via Hello! on 06/19/2000 at 13:42:31. Contact: ###-####.---s.e. corner of the building Interior walls ele. R/I 6/21/00 11:54:54 AM
ELE99-04403 Final6/19/20006/20/20006/20/2000 12:00:00 AMAPASS
###-#### Corrections completed 6/21/00 11:24:07 AM
ELE00-00840 Final6/19/20006/20/20006/20/2000 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 06/19/2000 at 16:13:14. Contact: ###-####. 4-plex; completed 6/21/00 11:54:24 AM
ELE00-02318 Final6/20/20006/20/20006/20/2000 12:00:00 AMPPASS
###-#### call first homeowner contractor-###-#### will be there till 2:30 Hot tub 6/21/00 11:30:03 AM
ELE00-02322 Temporary Service6/20/20006/20/20006/20/2000 12:00:00 AMPPASS
###-#### Temp. pole 6/21/00 11:31:44 AM
ELE00-00888 Electrical Rough-In6/20/20006/20/20006/20/2000 12:00:00 AMPPART
grounding ###-#### Grounding to electrode; underground 6/21/00 11:29:58 AM
ELE00-00340 Final6/20/20006/20/20006/20/2000 12:00:00 AMPFAIL
###-#### DAVE No access; called contractor, used wrong case number, and contractor didn't perform roof-top A/C unit installation. 6/21/00 11:30:59 AM