BLD01-01088
| FIRE-Final Inspection | 6/20/2001 | 6/20/2001 | 6/20/2001 12:00:00 AM | A | PASS |
|
|
Scheduled by Inspector: 409 On 6/20/2001 10:25:29 AM
|
BLD01-00239
| FIRE-Final Inspection | 6/20/2001 | 6/20/2001 | 6/20/2001 12:00:00 AM | P | FAIL |
|
|
Scheduled by Inspector: 409 On 6/20/2001 2:18:27 PM need 90 minute doors in area separation wall; smoke seals 6/20/2001 2:19:40 PM
|
BLD01-00293
| FIRE-Final Inspection | 6/20/2001 | 6/20/2001 | 6/20/2001 12:00:00 AM | P | FAIL |
|
|
Scheduled by Inspector: 409 On 6/20/2001 2:21:46 PM sprinkler required in new pass through room 6/20/2001 2:22:19 PM
|
BLD00-03472
| FIRE-Final Inspection | 6/20/2001 | 6/20/2001 | 6/20/2001 12:00:00 AM | P | FAIL |
|
|
Added by Inspector: 409 On 6/20/2001 2:25:42 PM need city approved plans and alarms completed; need manual release for preaction system
|
FIR01-00305
| INSP-Sprinkler Rough-in | 6/20/2001 | 6/20/2001 | 6/20/2001 12:00:00 AM | P | PART |
|
|
Added by Inspector: 409 On 6/20/2001 2:55:55 PM FDC complete to street
|
FIR01-00039
| INSP-Final Inspection | 6/11/2001 | 6/20/2001 | 6/20/2001 12:00:00 AM | P | PASS |
|
|
fire fn s.e. murdock- ###-#### fire alarms okay 6/20/2001 2:18:49 PM
|
FIR01-00069
| INSP-Final Inspection | 6/11/2001 | 6/20/2001 | 6/20/2001 12:00:00 AM | P | PASS |
|
|
s e murdock ###-#### fire fn
|
FIR00-00530
| INSP-Final Inspection | 6/11/2001 | 6/20/2001 | 6/20/2001 12:00:00 AM | P | PASS |
|
|
s e murdock ###-#### fire fn
|
FIR00-00637
| INSP-Final Inspection | 6/11/2001 | 6/20/2001 | 6/20/2001 12:00:00 AM | P | PASS |
|
|
s e murdock ###-#### fire fn
|
FIR00-00635
| INSP-Final Inspection | 6/11/2001 | 6/20/2001 | 6/20/2001 12:00:00 AM | P | FAIL |
|
|
s e murdock ###-#### fire fn need manual release for preaction system and detectors moved to ceiling 6/20/2001 2:26:28 PM
|