Inspections for the day of: Thursday, June 20, 2002.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE02-01281 Final6/19/20026/20/20026/20/2002 12:00:00 AMAPASS
JOHN ###-#### ok 6/20/2002 10:22:39 AM
ELE02-01781 Electrical Rough-In6/19/20026/20/20026/20/2002 12:00:00 AMAFAIL
MARV ###-#### CALL FIRST ALL WORK IS OUT SIDE cor. posted called 356.30#(2) strap sealthight flex, 342.46,352.46 bushings,and300.10 locknuts and nipples shall be made up tight at pump bell box and jbox on wall 6/20/2002 11:34:10 AM
ELE02-01764 Electrical Rough-In6/19/20026/20/20026/20/2002 12:00:00 AMAPART
###-#### ceiling ok called seal ko s, strap flex and mc in 2 areas 6/20/2002 1:43:22 PM
ELE02-01340 Final6/19/20026/20/20026/20/2002 12:00:00 AMAPASS
ELEN ###-#### PLEASE CALL BEFORE SO ELEN CAN MEET YOU THERE ok 6/20/2002 10:53:19 AM
ELE02-01340 Permanent Service6/20/20026/20/20026/20/2002 12:00:00 AMAPASS

p/s o/h rec. ok
ELE02-01874 Electrical Rough-In6/20/20026/20/20026/20/2002 12:00:00 AMPPART
wall back of store 6/20/2002 2:08:23 PM
ELE02-01855 Permanent Service6/20/20026/20/20026/20/2002 12:00:00 AMPPASS


p/s o/h new ok
ELE02-01742 Rough-In Permanent Service6/20/20026/20/20026/20/2002 12:00:00 AMPFAIL
cor. posted called 110.3(B) replace cut neutral bus both sub panels, and replace all 2,3,4 gang boxes with broken out internal cable clamps 110.26(F)(1)(a)shall move water piping, or sub panel for dedicated space below panel, 300.4 300.14 6 inches lenght of free conductor kit. in road front unit 6/20/2002 4:58:47 PM
ELE02-01855 Final6/20/20026/20/20026/20/2002 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 06/20/2002 at 07:41:32. Contact: ###-####. see added p/s inspection 6/20/2002 4:01:47 PM
ELE02-01867 Rough-In Permanent Service6/20/20026/20/20026/20/2002 12:00:00 AMPPASS
steve ###-#### r/i ok


p/s u/g new ok 6/20/2002 3:11:23 PM
ELE02-01086 Electrical Rough-In6/20/20026/20/20026/20/2002 12:00:00 AMPPART
LIGHT POLE BASES ###-#### BRANDON u/g and all pole bases 6/20/2002 3:34:04 PM