FIR02-00123
| INSP-Sprinkler Rough-in/Hydro | 6/19/2002 | 6/20/2002 | 6/21/2002 12:00:00 AM | P | PART |
|
|
Scheduled by a contractor via Hello! on 06/19/2002 at 08:48:35. Contact: ###-####. okay to cover 6/21/2002 10:28:07 AM
|
FIR02-00071
| INSP-Final Inspection | 6/19/2002 | 6/20/2002 | 6/20/2002 12:00:00 AM | A | FAIL |
|
|
Scheduled by Inspector: 409 On 6/19/2002 10:43:31 AM elevator has primary recall and no shunt; map at annunciator; zones defined at panel; keys for knox box 6/20/2002 10:00:57 AM
|
BLD01-01469
| FIRE-Final Inspection | 6/19/2002 | 6/20/2002 | 6/20/2002 12:00:00 AM | P | CANC |
|
|
Scheduled by a contractor via Hello! on 06/19/2002 at 13:17:46. Contact: ###-####.
|
FIR01-00478
| INSP-Final Inspection | 6/20/2002 | 6/20/2002 | 6/20/2002 12:00:00 AM | P | FAIL |
|
|
###-#### tested alarm horns - okay; need sprinkler bell working; 6/20/2002 4:33:17 PM
|
BLD02-00815
| FIRE-Final Inspection | 6/20/2002 | 6/20/2002 | 6/20/2002 12:00:00 AM | P | PASS |
|
|
MARK ###-#### will have "Door to remain..." sign above main entrance; keyed lock at main door and fire extinguisher for structural 6/20/2002 10:53:52 AM
|
FIR02-00126
| INSP-Final Inspection | 6/20/2002 | 6/20/2002 | 6/20/2002 12:00:00 AM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 06/20/2002 at 10:11:17. Contact: ###-####.
|
BLD02-00729
| FIRE-Final Inspection | 6/20/2002 | 6/20/2002 | 6/20/2002 12:00:00 AM | P | PASS |
|
|
Added by Inspector: 409 On 6/20/2002 1:32:57 PM
|
FIR01-00422
| INSP-Final Inspection | 6/20/2002 | 6/20/2002 | 6/20/2002 12:00:00 AM | P | FAIL |
|
|
Added by Inspector: 409 On 6/20/2002 4:31:16 PM outside bell not working; need canopies
|
BLD01-00641
| FIRE-Final Inspection | 6/20/2002 | 6/20/2002 | 6/20/2002 12:00:00 AM | P | FAIL |
|
|
Added by Inspector: 409 On 6/20/2002 4:32:21 PM need adress; fire bell not working; canopies for sprinklers; smoke detectors - some need batteries
|
FIR02-00028
| INSP-Final Inspection | 6/19/2002 | 6/20/2002 | 6/20/2002 12:00:00 AM | P | FAIL |
|
|
fire fn - orlin- ###-#### cell heat detector within 24 inches of sprinkler head; knox box; map for FACP; descriptors not labeled properly 6/20/2002 4:11:23 PM
|