FIR00-00390
| FIR-Aging Inspection | 6/20/2003 | 6/20/2003 | 6/20/2003 12:00:00 AM | | PART |
|
|
I spoke to Laura with SimplexGrinnell and she was going to research the project and contact me about the job status 6/20/2003 8:51:34 AM
|
MIS03-00125
| FIR-Final | 6/19/2003 | 6/20/2003 | 6/20/2003 12:00:00 AM | A | PASS |
|
|
fire life safety finaled 6/20/2003 12:04:32 PM
|
FIR03-00128
| INSP-Sprinkler Rough-in/Hydro | 6/19/2003 | 6/20/2003 | 6/20/2003 12:00:00 AM | A | CANC |
|
|
wrong inspection called in per Mike with Debest. This job is not ready yet 6/20/2003 8:50:03 AM
|
FIR03-00049
| INSP-Final Inspection | 6/18/2003 | 6/20/2003 | 6/20/2003 12:00:00 AM | P | FAIL |
|
|
provide tamper switch o the anti-freeze system control valve. Strobes do not sync. Change 110cd strobe to 30cd. Provide verification the ceiling strobes are ok for wall use. Provide a map for the facp. Provide knox key box. 6/20/2003 12:09:58 PM
|
FIR03-00207
| INSP-Final Inspection | 6/18/2003 | 6/20/2003 | 6/20/2003 12:00:00 AM | P | FAIL |
|
|
provide tamper switch o the anti-freeze system control valve. Strobes do not sync. Change 110cd strobe to 30cd. Provide verification the ceiling strobes are ok for wall use. Provide a map for the facp. Provide knox key box. 6/20/2003 12:10:07 PM
|
FIR03-00087
| INSP-Final Inspection | 6/20/2003 | 6/20/2003 | 6/20/2003 12:00:00 AM | P | PASS |
|
|
fire sprinklers finaled 6/20/2003 1:43:48 PM
|
FIR03-00193
| INSP-Final Inspection | 6/20/2003 | 6/20/2003 | 6/20/2003 12:00:00 AM | P | PASS |
|
|
fire alarm finaled. Zone 3 on the fire alarm panel failed. Wires were transfered to zone 5 which was a spare. The owner was notified 6/20/2003 12:51:54 PM
|
FIR03-00170
| INSP-Final Inspection | 6/20/2003 | 6/20/2003 | 6/20/2003 12:00:00 AM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 6/20/2003 at 8:32:23 AM. Contact: ###-####.
|
FIR03-00175
| INSP-Sprinkler Rough-in/Hydro | 6/20/2003 | 6/20/2003 | 6/20/2003 12:00:00 AM | P | PASS |
|
|
Dry system and underground hydro tests are OK 6/20/2003 12:12:06 PM
|
FIR00-00419
| INSP-Sprinkler Rough-in/Hydro | 6/20/2003 | 6/20/2003 | 6/20/2003 12:00:00 AM | P | CANC |
|
|
contractor said the sprinkler piping has a leak so the hydro test could not be performed 6/20/2003 1:49:14 PM
|