ELE05-01280
| ELE-Aging Inspection | 6/20/2005 | 6/20/2005 | 6/21/2005 9:53:18 AM | | PART |
|
|
WSUC
|
ELE05-01729
| Final | 6/17/2005 | 6/20/2005 | 6/20/2005 3:47:59 PM | P | FAIL |
|
|
Phone #: ###-#### Internet Inspection Request from: Tawnya McKinney no access to roof and needs to support disconnect called
|
ELE04-03054
| Electrical Rough-In | 6/20/2005 | 6/20/2005 | 6/20/2005 3:34:23 PM | P | PART |
|
|
BASEMENT CEILING INSPECTION PLEASE @ OXFORD SUITES; Phone #: ###-#### Internet Inspection Request from: Barry Kendall hard ceiling ok anop
|
ELE05-02149
| Electrical Rough-In | 6/20/2005 | 6/20/2005 | 6/20/2005 2:51:21 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 6/20/2005 at 9:43:26 AM. Contact: ###-####. walls and ceiling ok
|
ELE05-02165
| Electrical Rough-In | 6/20/2005 | 6/20/2005 | 6/20/2005 2:17:53 PM | P | PASS |
|
|
###-#### - jerry 110.26(F)(1) remove t/v from below p/s and provide grd for t/v and phone r/i ok
|
ELE05-01975
| Electrical Rough-In | 6/17/2005 | 6/20/2005 | 6/20/2005 1:41:33 PM | P | PASS |
|
|
wall cover inspection, please contact Gene, thank you.; Phone #: ###-#### Internet Inspection Request from: Wendy Waters ok
|
ELE05-01443
| Rough-In Permanent Service | 6/20/2005 | 6/20/2005 | 6/20/2005 1:41:09 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 6/20/2005 at 10:38:21 AM. no r/i p/s o/h rec. ok
|
ELE05-02167
| Temporary Service | 6/20/2005 | 6/20/2005 | 6/20/2005 1:01:32 PM | P | PASS |
|
|
paula ###-#### t/s u/g new ok
|
ELE05-02126
| Rough-In Permanent Service | 6/20/2005 | 6/20/2005 | 6/20/2005 12:38:27 PM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 6/20/2005 at 8:13:20 AM. Contact: ###-####. cor posted called needs concrete encased electrode, 210.70 install required fixtures all exits exterior side, 410.30 (C)(1) 1&2, cord shall be cord cap and recept, 250.12 clean paint where grd or bond to metal
|
ELE05-02164
| Temporary Service | 6/20/2005 | 6/20/2005 | 6/20/2005 12:00:02 PM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Joe Thomas t/s u/g new ok
|
ELE05-02113
| Electrical Rough-In | 6/17/2005 | 6/20/2005 | 6/20/2005 10:01:18 AM | A | PART |
|
|
drop ceiling grid inspection///darel; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa ceiling ok
|
ELE05-02029
| Electrical Rough-In | 6/17/2005 | 6/20/2005 | 6/20/2005 9:22:56 AM | A | PASS |
|
|
Work being done at 1107 W. 8th St.; Phone #: ###-#### Internet Inspection Request from: Dana Moyer ok corrections made
|
ELE05-02163
| Electrical Rough-In | 6/17/2005 | 6/20/2005 | 6/20/2005 8:52:38 AM | A | PASS |
|
|
Added new circuits for kitchen range, dishwasher, appliance circuits, micro/hood. New addition of dining room and front porch. Panel is located in laundry room next to the kitchen.; Phone #: ###-#### Internet Inspection Request from: Joe Thomas ok
|
ELE05-01406
| Final | 6/17/2005 | 6/20/2005 | 6/20/2005 8:16:46 AM | A | PASS |
|
|
chuck ###-#### ok
|
ELE05-02128
| Rough-In Permanent Service | 6/17/2005 | 6/20/2005 | 6/20/2005 7:53:44 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Ryan Christensen r/i ok p/s u/g new ok
|
ELE05-02029
| Final | 6/20/2005 | 6/20/2005 | 6/20/2005 12:00:00 AM | A | PASS |
|
|
ok
|