ELE05-02174
| Electrical Rough-In | 6/20/2005 | 6/20/2005 | 6/20/2005 4:21:35 PM | P | PASS |
|
|
doug ###-#### ok to cover new wall only, called contractor about un-supported boxes in ceiling, and need for gfci in kitchen
|
ELE05-01040
| Final | 6/20/2005 | 6/20/2005 | 6/20/2005 4:11:49 PM | P | PASS |
|
|
This is the final thanks Bob. Call Dennis with any questions.; Phone #: ###-#### Internet Inspection Request from: Daniel Gamboa ok to final, signed occ. card
|
ELE05-02177
| Rough-In Permanent Service | 6/20/2005 | 6/20/2005 | 6/20/2005 2:07:42 PM | P | PASS |
|
|
alan ###-#### told elect to flush mount garage boxes, ric ok, p/s u/g n ok
|
ELE05-01180
| Final | 6/20/2005 | 6/20/2005 | 6/20/2005 1:33:52 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 6/20/2005 at 7:49:23 AM. Contact: ###-####. called contr, left message, left survey, 210.8(A)(1) bathroom recpt shall be gfci
|
ELE05-01931
| Electrical Rough-In | 6/20/2005 | 6/20/2005 | 6/20/2005 12:59:30 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 6/20/2005 at 8:11:33 AM. Contact: ###-####. u/g for gec ok to cover
|
ELE05-01690
| Final | 6/20/2005 | 6/20/2005 | 6/20/2005 11:53:49 AM | A | PART |
|
|
Ready for one time inspection, job is complete and corrections have been made. Thank you.; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH ok to final, corrections done, check back to see surge suppressor installed on west brake
|
ELE04-03161
| Final | 6/17/2005 | 6/20/2005 | 6/20/2005 11:04:17 AM | A | PASS |
|
|
ed; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie had contr put in correct fuses, straps. ok to final
|
ELE05-01690
| Electrical Rough-In | 6/17/2005 | 6/20/2005 | 6/20/2005 10:18:54 AM | A | CANC |
|
|
Ready for one time inspection, job is complete and corrections have been made. Thank you.; Phone #: ###-#### Internet Inspection Request from: BRIAN see final
|
ELE05-02008
| Electrical Rough-In | 6/19/2005 | 6/20/2005 | 6/20/2005 9:32:06 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 6/19/2005 at 11:20:11 PM. Contact: ###-####. u/g ok, equipotential bond ok to cover
|
ELE05-01098
| Permanent Service | 6/18/2005 | 6/20/2005 | 6/20/2005 8:40:04 AM | A | FAIL |
|
|
Scheduled by a contractor via Hello! on 6/18/2005 at 7:19:01 PM. Contact: ###-####. called, left message, left corr notice, 300.4(F) & 344.46 Bushings shall be provided to protect wire from abrasion, 312.5 gec shall be protected from abrasion, 352.30 rnc shall be strapped within 3' of panel
|
ELE05-02160
| Temporary Service | 6/17/2005 | 6/20/2005 | 6/20/2005 8:23:21 AM | A | PASS |
|
|
###-#### - rick t/s u/g n ok
|
ELE05-02091
| Rough-In Permanent Service | 6/17/2005 | 6/20/2005 | 6/20/2005 8:10:50 AM | A | PASS |
|
|
darel; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa ric ok, p/s u/g n ok
|