Inspections for the day of: Monday, June 20, 2005.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR03-00091 FIR-Aging Inspection6/20/20056/20/20056/21/2005 3:13:34 PM DONE
Spoke with Mike Bierman at Shilo in regards to this open permit, also called and left a message with Trent Bice. Mike is to follow up with an inspection request.
FIR05-00190 INSP-Sprinkler Rough-in/Hydro6/20/20056/20/20056/20/2005 5:09:59 PMPFAIL
Pendent heads are blocked by proximity to columns in womens lockers GS202, two heads are supplied by a 1" feed in womens GS203- see note #12 on plan review comments for requirements. Heads circled in red on approved plans are the only areas inspected at this time.
BLD04-01882 FIRE-Final Inspection6/20/20056/20/20056/20/2005 3:03:48 PMPFAIL
Missing door hardware, need to test duct smoke detectors, exit discharge lighting not working, missing max occ. signs, need to test hood system which is not ready.
BLD04-01051 BLD-Final6/20/20056/20/20056/20/2005 2:58:06 PMPFAIL
Exit discharge lighting at three locations did not operate under emergency power, max occ. signs not installed, not all door hardware has been installed , still need to test duct smoke detectors and annunciators, hood suppresion system not ready to test.
FIR05-00282 INSP-Sprinkler Rough-in/Hydro6/20/20056/20/20056/20/2005 1:00:24 PMAPART
Overhead hydrostatic test passed inspection.
FIR04-00788 INSP-Final Inspection6/20/20056/20/20056/20/2005 12:58:55 PMPPASS
Fire alarm finaled.
FIR05-00318 INSP-Final Inspection6/17/20056/20/20056/20/2005 9:08:16 AMAFAIL
Tested security doors on first floor. Unable to test doors on 2nd, 3rd, or 5th due to lack of locking function verification.
BLD04-00159 FIRE-Final Inspection6/20/20056/20/20056/20/2005 12:00:00 AMPPASS
Fire life safety finaled.
BLD04-00313 FIRE-Final Inspection6/20/20056/20/20056/20/2005 12:00:00 AMPPASS
Fire life safety finaled.
FIR05-00282 INSP-Sprinkler Rough-in6/20/20056/20/20056/20/2005 12:00:00 AMPFAIL
Verify correct size orfice on inspectors test, verify sammy screw size is listed for 2 1/2" pipe attatched vertically, overspaced longitudinal EQ brace, SSU above break room is too far below deck, provide as-builts for added head at entry and in accounting room, verify uprights after paint paper is removed, check L09 for blockage per. NFPA 8.6.5.1.2 at exposed beam- possibly not meeting density req. from L08.