FIR06-00152
| FIR-Aging Inspection | 6/20/2006 | 6/20/2006 | 6/23/2006 2:33:41 PM | | PASS |
|
|
permit finaled
|
BLD05-02018
| FIRE-Final Inspection | 6/19/2006 | 6/20/2006 | 6/21/2006 9:12:12 AM | P | FAIL |
|
|
Need two letters from engineers as per the review comments. Fire dept. access road does not meet the agreed upon 17' width. Also need to final sprinklers and alarm.
|
FIR06-00200
| INSP-Sprinkler Rough-in/Hydro | 6/20/2006 | 6/20/2006 | 6/20/2006 3:43:58 PM | P | CANC |
|
|
Wrong permit number called in
|
FIR06-00429
| INSP-Final Inspection | 6/20/2006 | 6/20/2006 | 6/20/2006 3:40:25 PM | P | FAIL |
|
|
Inspection was meant to be a rough-in inspection. Piping is ok to cover.
|
BLD04-00469
| BLD-Aging Inspection | 6/20/2006 | 6/20/2006 | 6/20/2006 3:39:18 PM | | NR |
|
|
|
FIR05-00755
| INSP-Final Inspection | 6/19/2006 | 6/20/2006 | 6/20/2006 2:07:24 PM | P | FAIL |
|
|
15/75 strobes are being used which leaves alot of spacing issues. Also in the second floor corridor elevation changes block visuals. One additional stobe will need to be added as discussed. Sound levels are ok. Duct detectors are ok.
|
FIR06-00290
| INSP-Final Inspection | 6/19/2006 | 6/20/2006 | 6/20/2006 1:59:02 PM | A | PASS |
|
|
Permit finaled
|
BLD05-02584
| FIRE-Final Inspection | 6/20/2006 | 6/20/2006 | 6/20/2006 11:59:10 AM | P | PASS |
|
|
Life safety finaled
|