Inspections for the day of: Tuesday, June 20, 2006.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00152 FIR-Aging Inspection6/20/20066/20/20066/23/2006 2:33:41 PM PASS
permit finaled
BLD05-02018 FIRE-Final Inspection6/19/20066/20/20066/21/2006 9:12:12 AMPFAIL
Need two letters from engineers as per the review comments. Fire dept. access road does not meet the agreed upon 17' width. Also need to final sprinklers and alarm.
FIR06-00200 INSP-Sprinkler Rough-in/Hydro6/20/20066/20/20066/20/2006 3:43:58 PMPCANC
Wrong permit number called in
FIR06-00429 INSP-Final Inspection6/20/20066/20/20066/20/2006 3:40:25 PMPFAIL
Inspection was meant to be a rough-in inspection. Piping is ok to cover.
BLD04-00469 BLD-Aging Inspection6/20/20066/20/20066/20/2006 3:39:18 PM NR
FIR05-00755 INSP-Final Inspection6/19/20066/20/20066/20/2006 2:07:24 PMPFAIL
15/75 strobes are being used which leaves alot of spacing issues. Also in the second floor corridor elevation changes block visuals. One additional stobe will need to be added as discussed. Sound levels are ok. Duct detectors are ok.
FIR06-00290 INSP-Final Inspection6/19/20066/20/20066/20/2006 1:59:02 PMAPASS
Permit finaled
BLD05-02584 FIRE-Final Inspection6/20/20066/20/20066/20/2006 11:59:10 AMPPASS
Life safety finaled