Inspections for the day of: Wednesday, June 20, 2007.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-01615 Rough-In Permanent Service6/20/20076/20/20076/20/2007 3:32:45 PMPPASS
Gene - ###-#### Phone #: ###-#### Internet Inspection Request from: Tracy Robertson r/i p/s u/g new ok
ELE07-02208 Electrical Rough-In6/20/20076/20/20076/20/2007 2:17:07 PMPPART
vern - pls call 30 mins prior; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang called left message 6" free length, and terminate all equip grds together
r/i ok
ELE07-02043 Electrical Rough-In6/19/20076/20/20076/20/2007 1:35:49 PMPPASS
steve - 2nd half underground inspection - late afternoon please Phone #: ###-####
all u/g ok
ELE07-02206 Rough-In Permanent Service6/20/20076/20/20076/20/2007 1:09:55 PMPPASS
Rough In and Service Phone #: ###-#### Internet Inspection Request from: Rowdy Monroe p/s u/g new ok
ELE07-02201 Permanent Service6/19/20076/20/20076/20/2007 12:45:44 PMPPART
electrician is Mike McCarrel Phone #: ###-#### Internet Inspection Request from: Jarrod Clymer no p/s conference ok
ELE07-02182 Permanent Service6/19/20076/20/20076/20/2007 10:55:04 AMAPASS
electrician is Nick Felsted Phone #: ###-#### Internet Inspection Request from: Jarrod Clymer see added r/i for corr
p/s u/g new ok
ELE07-02182 Electrical Rough-In6/20/20076/20/20076/20/2007 10:54:27 AMPFAIL
electrician is Nick Felsted Phone #: ###-#### Internet Inspection Request from: Jarrod Clymer300.4 nail plates and 11/4" for SER garage, 312.5 conn for SER at p/s, and MNB not allowed in conduit from subpanel to basement old p/s jbox, 300.3(B) pump wiring, 250.52(A) jumper around flex wter pipe basement, 110.12(A) seal all unused KOs and conduits, church shall secure licensed elect contr to install u/g for pole light, all pole light wiring in violation covered before inspection no permit
ELE07-02183 Electrical Rough-In6/20/20076/20/20076/20/2007 9:53:57 AMANR
Scheduled by a contractor via Hello! on 6/20/2007 at 7:03:29 AM. Contact: ###-####. called protect cables and ENT 300.4 install all low voltage before r/i requested, address box fill, need documentation from governing body of facility if any area is patient care, bld permit states medical
ELE07-01364 Electrical Rough-In6/19/20076/20/20076/20/2007 9:21:32 AMAPART
chris - ceiling cover Phone #: ###-####
grid ceilings ok correction posted for cable hung fixtures hard ceiling 410.30(C)(1) & 100.3(B) shall follow manufactures instructions and use manufactures listed canopy for fixtures called
ELE07-02206 Electrical Rough-In6/20/20076/20/20076/20/2007 8:35:19 AMAPASS
Scheduled by a contractor via Hello! on 6/20/2007 at 5:21:55 AM. Contact: ###-####. ok
ELE07-02053 Permanent Service6/19/20076/20/20076/20/2007 8:03:44 AMAPASS
Scheduled by a contractor via Hello! on 6/19/2007 at 4:31:58 PM. Contact: ###-####. p/s o/h new ok
ELE07-02201 Permanent Service6/19/20076/20/20076/19/2007 1:13:30 PMACANC
electrician is Mike McCarrel Phone #: ###-#### Internet Inspection Request from: Jarrod Clymer Inspection cancelled from web by: Jarrod Clymer