Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-00933 ELE-Aging Inspection6/20/20076/20/20076/25/2007 9:41:42 AM DONE
see final
ELE07-01436 Final6/19/20076/20/20076/20/2007 3:27:37 PMPPASS
jerod Note: please call 1/2 hr prior to inspection Phone #: ###-#### corr made, ok to final
ELE07-02200 Temporary Service6/20/20076/20/20076/20/2007 2:48:14 PMPPASS
greg; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang corr made, t/s o/h n ok
ELE07-02226 Final6/20/20076/20/20076/20/2007 2:19:01 PMPPASS
shane; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang ok to final, no card to sign
ELE07-02192 Temporary Service6/20/20076/20/20076/20/2007 1:39:43 PMPFAIL
steve; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang called, added to corr notice, corrections not made, created more, 250.46(C) gec shall be continuous, 250.55 gec per table #2, on 200a disc, 250.92(B) bonding shall be provided for service, 110.14 connection such as scraping paint for lugs, fee due
ELE07-02173 Permanent Service6/20/20076/20/20076/20/2007 12:45:36 PMPFAIL
joe Phone #: ###-#### called , corrections not done plus created new violations, nec 312.5 shall provide abrasion protection for all conductors entering enclosures, 250.64(C) shall use irreversible splice on gec, did not fix panel door or ground water pipe,fee due
ELE07-02040 Permanent Service6/19/20076/20/20076/20/2007 10:48:31 AMAPASS
Key is under rock that is right of the stairs at the front door, need inspection on new 200A sevice and panel to get reconnected. Phone #: ###-#### Internet Inspection Request from: Lynn Cable p/s o/h rec ok
ELE07-02003 Final6/19/20076/20/20076/20/2007 10:04:52 AMAPASS
Please inspect the circuit to the a/c. Thanks Phone #: ###-#### x0000 Internet Inspection Request from: BRIAN KEITH ok to final
ELE07-01950 Final6/18/20076/20/20076/20/2007 9:31:18 AMAPASS
MITCH PAGE - WILL MEET @ JOBSITE Phone #: ###-#### Internet Inspection Request from: Randy Vail ok to final
ELE07-02095 Electrical Rough-In6/19/20076/20/20076/20/2007 9:01:15 AMAPART
skip ###-#### walls anop ok to cover, held back for fa, north 1/3 area 2nd floor
ELE07-02063 Electrical Rough-In6/19/20076/20/20076/20/2007 7:51:36 AMAPASS
Scheduled by a contractor via Hello! on 6/19/2007 at 10:17:42 PM. Contact: ###-####. ric walls only ok