Inspections for the day of: Wednesday, June 20, 2007.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-00032 FIR-Aging Inspection6/20/20076/20/20076/22/2007 10:03:46 AM DONE
Work in progress.
FIR07-00316 INSP-Sprinkler Rough-in6/20/20076/20/20076/21/2007 10:35:25 AMPNR
Work is not ready for inspection.
FIR06-00948 INSP-Final Inspection6/20/20076/20/20076/20/2007 2:47:32 PMPPASS
Corrections verified for compliance, fire sprinkler permit finaled.
FIR07-00203 INSP-Sprinkler Rough-in/Hydro6/19/20076/20/20076/20/2007 1:10:55 PMAPART
Begin dry sytem air test @ 45 psi. at 11:50 am.
FIR07-00203 INSP-Sprinkler Rough-in6/19/20076/20/20076/20/2007 1:09:45 PMAPART
Begin dry system air test at 45psi.
BLD06-03008 FIRE-Final Inspection6/19/20076/20/20076/20/2007 11:34:47 AMAFAIL
Need to provide one fire extinguisher for each floor level with current certification tag.
BLD06-00147 FIRE-Final Inspection6/19/20076/20/20076/20/2007 11:26:12 AMAPASS
Fire life safety is acceptable, approved door hardware at the back exit to be installed prior to structrual final per agreement with contractor, J. Storey to verify.
BLD07-00677 FIRE-Final Inspection6/19/20076/20/20076/20/2007 10:48:43 AMAPASS
Fire life safety inspection passed, suite number signage to be posted when wall paint finishes are complete.
BLD07-00678 FIRE-Final Inspection6/19/20076/20/20076/20/2007 10:47:10 AMAPASS
Fire life safety passed final inspection, permanent suite signage to be installed once paint finishes are complete.