FIR11-00219
| INSP-Alarm Testing | 6/16/2011 | 6/17/2011 | | A | |
|
|
Phone #: ###-#### >> Inspection requested via web by Robert Gobler
|
FIR05-00538
| FIR-Aging Inspection | 6/20/2011 | 6/20/2011 | 6/20/2011 3:56:47 PM | | DONE |
|
|
|
FIR06-00088
| FIR-Aging Inspection | 6/20/2011 | 6/20/2011 | 6/20/2011 3:56:34 PM | | FAIL |
|
|
Ref. correction items.
|
FIR06-00179
| FIR-Aging Inspection | 6/20/2011 | 6/20/2011 | 6/20/2011 3:56:10 PM | | FAIL |
|
|
No call for insp.
|
FIR11-00190
| INSP-Final Inspection | 6/20/2011 | 6/20/2011 | 6/20/2011 3:53:21 PM | A | NR |
|
|
Final pending current annual inspection for the existing system riser, pressure switch at the dry system does not activate the outside bell, provide QR style heads at the spare head cabinet.
|
BLD11-00340
| FIRE-Final Inspection | 6/20/2011 | 6/20/2011 | 6/20/2011 3:43:59 PM | P | FAIL |
|
|
Noted items include; post max. occupant load signs at the main and mezzanine levels, revise hardware at door #104, project related fire alarm and sprinkler permit finals pending.
|
FIR11-00219
| INSP-Final Inspection | 6/20/2011 | 6/20/2011 | 6/20/2011 3:40:27 PM | P | NR |
|
|
Pending corrections.
|
FIR11-00219
| INSP-Alarm Testing | 6/20/2011 | 6/20/2011 | 6/20/2011 3:36:30 PM | A | PART |
|
|
Functional testing of the new fire alarm panel and system completed satisfactory. Final pending item # 8 and 31 on the fire code review notes.
|
FIR11-00287
| INSP-Conference | 6/20/2011 | 6/20/2011 | 6/20/2011 3:33:31 PM | P | DONE |
|
|
Regarding project inspection schedule.
|
BLD11-01120
| FIRE-Final Inspection | 6/17/2011 | 6/20/2011 | 6/20/2011 3:32:34 PM | A | PASS |
|
|
C/N items finished. Fire life safety finaled.
|
FIR10-00659
| INSP-Final Inspection | 6/20/2011 | 6/20/2011 | 6/20/2011 3:31:29 PM | P | PASS |
|
|
Verified plan modification and installation of new SW heads and piping at the bonus room above the garage. System charged while on site. Permit finaled.
|
BLD11-01069
| FIRE-Final Inspection | 6/20/2011 | 6/20/2011 | 6/20/2011 3:29:13 PM | P | FAIL |
|
|
See review notes items #2, 4 and 8 including door hardware at the main entry vestibule and east warehouse exit doors in need of revision, fire extinguishers are overdue annual certification by three years, permit documents indicate the building is fully fire sprinklered- however two offices, the vaults and the east warehouse area are not sprinklered. Advised tenant to contact plan review regarding provisions and requirements for fire sprinkler and main door exit hardware issues.
|
FIR11-00190
| INSP-Final Inspection | 6/17/2011 | 6/20/2011 | 6/20/2011 12:00:00 AM | A | CANC |
|
|
Dennis Thomas or ###-#### Ron Stenquist Phone #: ###-####
|