PLM16-02140
| Groundwork | 6/20/2016 | 6/20/2016 | 6/20/2016 3:32:42 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Ann Marie Reyes
|
PLM16-02147
| Groundwork | 6/20/2016 | 6/20/2016 | 6/20/2016 3:32:26 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Ann Marie Reyes
|
PLM16-02148
| Groundwork | 6/20/2016 | 6/20/2016 | 6/20/2016 3:31:51 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Ann Marie Reyes
|
PLM16-02149
| Groundwork | 6/20/2016 | 6/20/2016 | 6/20/2016 3:31:35 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Ann Marie Reyes
|
PLM16-01249
| Other | 6/20/2016 | 6/20/2016 | 6/20/2016 3:13:03 PM | P | PASS |
|
|
tenting inspection Inspection requested via web by Brian Johansen >tenting over water lines ok
|
PLM16-02167
| Water and/or Sewer | 6/17/2016 | 6/20/2016 | 6/20/2016 2:29:17 PM | P | FAIL |
|
|
Juve Ayala is contact for back flow inspection. give him an hour advance notice so he can meet inspector Phone #: ###-#### Inspection requested via web by Nick Louie >need to certify backflow at 2008
|
PLM16-02200
| Water and/or Sewer | 6/17/2016 | 6/20/2016 | 6/20/2016 2:28:37 PM | P | FAIL |
|
|
Juve Ayala is contact for back flow inspection. give him an hour advance notice so he can meet inspector Phone #: ###-#### Inspection requested via web by Nick Louie >need to certify backflow
|
PLM16-02188
| Water and/or Sewer | 6/17/2016 | 6/20/2016 | 6/20/2016 2:26:13 PM | P | CANC |
|
|
Juve Ayala is contact for back flow inspection. give him an hour advance notice so he can meet inspector Phone #: ###-#### Inspection requested via web by Nick Louie
|
PLM16-02188
| Sprinkler (Final) | 6/20/2016 | 6/20/2016 | 6/20/2016 2:25:48 PM | P | PASS |
|
|
Juve Ayala is contact for back flow inspection. give him an hour advance notice so he can meet inspector Phone #: ###-#### Inspection requested via web by Nick Louie
|
PLM16-02104
| Groundwork | 6/20/2016 | 6/20/2016 | 6/20/2016 1:43:26 PM | P | PASS |
|
|
>check remaining work
|
PLM16-02110
| Water Heater Final | 6/20/2016 | 6/20/2016 | 6/20/2016 1:30:04 PM | P | PASS |
|
|
Would like Early afternoon if possible, and a call when on way. Thank you!! Phone #: ###-#### Inspection requested via web by Xanti Berria
|
PLM16-02184
| Plumbing Rough-in | 6/19/2016 | 6/20/2016 | 6/20/2016 11:03:41 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Aarin Van Curen
|
PLM16-00424
| Final | 6/14/2016 | 6/20/2016 | 6/20/2016 10:41:20 AM | A | PASS |
|
|
Please call ###-#### when on way for him to meet you onsite Phone #: ###-#### Inspection requested via web by Ben Davis
|
PLM16-01189
| Final | 6/19/2016 | 6/20/2016 | 6/20/2016 10:15:03 AM | A | FAIL |
|
|
lock box code 23579 Phone #: ###-#### Inspection requested via web by Jeffrey Hankins >need to add all fixtures to permit. >valves at tankless wh installed upside down, shutoff cannot be between wh and t/p, cold wrong as well. >relief valve needs a 1" airgap >1/2" gas flex connector to small for btu's, needs to be 3/4".
|
PLM16-02111
| DOC - Permit Finaled | 6/20/2016 | 6/20/2016 | 6/20/2016 9:15:21 AM | P | PASS |
|
|
|
PLM16-02111
| Water and/or Sewer | 6/19/2016 | 6/20/2016 | 6/20/2016 9:14:51 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Gary Olson
|
PLM16-02101
| Sprinkler (Final) | 6/17/2016 | 6/20/2016 | 6/20/2016 8:59:11 AM | A | PASS |
|
|
would like call ahead; Jose Phone #: ###-####
|
PLM16-02104
| Groundwork | 6/14/2016 | 6/20/2016 | 6/20/2016 8:36:40 AM | A | PART |
|
|
CHRIS IS THE JOB CONTACT ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER >part gw is ok,
|
PLM15-03823
| DOC - Permit Finaled | 6/20/2016 | 6/20/2016 | 6/20/2016 7:55:06 AM | P | PASS |
|
|
|
PLM15-03823
| PLM-Aging Inspection | 6/20/2016 | 6/20/2016 | 6/20/2016 7:54:49 AM | | PASS |
|
|
work complete
|