Inspections for the day of: Monday, June 20, 2016.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR16-00339 INSP-Sprinkler Rough-in6/20/20166/20/20166/20/2016 2:40:42 PMPPASS
Rough to cover inspection complete for overhead fire sprinkler piping, overhead fire sprinkler piping approved for cover.
FIR16-00097 INSP-Final Inspection6/17/20166/20/20166/20/2016 2:17:03 PMPPART
Elevator recall/shunt tested, Audio visual devices tested on level 1, items left for inspection: smoke evacuation system and elevator smoke curtains.
FIR16-00129 INSP-Sprinkler Rough-in6/20/20166/20/20166/20/2016 11:09:42 AMPPASS
Rough to cover inspection for overhead fire sprinkler piping complete, notated area's approved for cover with pink highlighter/red ink on the city approved drawings, area's marked approved for cover.
BLD16-02154 FIRE-Final Inspection6/20/20166/20/20166/20/2016 10:52:10 AMPFAIL
Emergency lights that are currently in place did not operate with test button. Emergency lights are not required but if they are in place the need to be operable. Emergency lights need to be serviced or removed. Rear door is secured by a bar with bolts, this is not an approved method for securing the door, door hardware needs to have single action paddle type hardware or panic hardware installed.
BLD16-02099 FIRE-Final Inspection6/15/20166/20/20166/20/2016 10:12:00 AMAPASS
No fire sprinkler modifications, no fire alarm modifications, fine extinguisher is in place with current inspection tag (elevator lobby). Final life fire safety inspection passed/complete.
FIR16-00346 INSP-Final Inspection6/20/20166/20/20166/20/2016 9:42:34 AMPPASS
Final fire sprinkler inspection passed/complete
BLD16-02069 FIRE-Final Inspection6/16/20166/20/20166/20/2016 9:32:23 AMAFAIL
Fire extinguisher needs to be inspected and tagged with current inspection tag. Exit signs/egress lighting that is currently in place does not work with test button, exit signs are not required so existing exits signs can be removed, if exit signs remain then they need to be serviced and operational.
BLD16-00067 FIRE-Final Inspection6/17/20166/20/20166/20/2016 9:08:51 AMAPASS
Fire sprinkler inspection complete, no fire alarm, discussed locations for inspected/tagged fire extinguishers. Final life fire safety inspection passed/complete.
FIR16-00184 INSP-Final Inspection6/20/20166/20/20166/20/2016 9:07:11 AMAPASS
Final fire sprinkler inspection passed/complete
FIR15-00808 INSP-Sprinkler Rough-in/Hydro6/17/20166/20/20166/20/2016 8:42:57 AMACANC
Inspection request re-scheduled per conversation with Mark, phone number ###-#### due to pressure loss for the hydrostatic test.
BLD15-04191 FIRE-Final Inspection6/17/20166/20/20166/20/2016 8:39:14 AMAPART
Level 2 fire sprinklers complete, level 2 fire alarms complete, fire extinguishers are in place with cuurent inspection tags for level 2, final life fire safety inspection for level 2 passed/complete.