FIR16-00339
| INSP-Sprinkler Rough-in | 6/20/2016 | 6/20/2016 | 6/20/2016 2:40:42 PM | P | PASS |
|
|
Rough to cover inspection complete for overhead fire sprinkler piping, overhead fire sprinkler piping approved for cover.
|
FIR16-00097
| INSP-Final Inspection | 6/17/2016 | 6/20/2016 | 6/20/2016 2:17:03 PM | P | PART |
|
|
Elevator recall/shunt tested, Audio visual devices tested on level 1, items left for inspection: smoke evacuation system and elevator smoke curtains.
|
FIR16-00129
| INSP-Sprinkler Rough-in | 6/20/2016 | 6/20/2016 | 6/20/2016 11:09:42 AM | P | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping complete, notated area's approved for cover with pink highlighter/red ink on the city approved drawings, area's marked approved for cover.
|
BLD16-02154
| FIRE-Final Inspection | 6/20/2016 | 6/20/2016 | 6/20/2016 10:52:10 AM | P | FAIL |
|
|
Emergency lights that are currently in place did not operate with test button. Emergency lights are not required but if they are in place the need to be operable. Emergency lights need to be serviced or removed. Rear door is secured by a bar with bolts, this is not an approved method for securing the door, door hardware needs to have single action paddle type hardware or panic hardware installed.
|
BLD16-02099
| FIRE-Final Inspection | 6/15/2016 | 6/20/2016 | 6/20/2016 10:12:00 AM | A | PASS |
|
|
No fire sprinkler modifications, no fire alarm modifications, fine extinguisher is in place with current inspection tag (elevator lobby). Final life fire safety inspection passed/complete.
|
FIR16-00346
| INSP-Final Inspection | 6/20/2016 | 6/20/2016 | 6/20/2016 9:42:34 AM | P | PASS |
|
|
Final fire sprinkler inspection passed/complete
|
BLD16-02069
| FIRE-Final Inspection | 6/16/2016 | 6/20/2016 | 6/20/2016 9:32:23 AM | A | FAIL |
|
|
Fire extinguisher needs to be inspected and tagged with current inspection tag. Exit signs/egress lighting that is currently in place does not work with test button, exit signs are not required so existing exits signs can be removed, if exit signs remain then they need to be serviced and operational.
|
BLD16-00067
| FIRE-Final Inspection | 6/17/2016 | 6/20/2016 | 6/20/2016 9:08:51 AM | A | PASS |
|
|
Fire sprinkler inspection complete, no fire alarm, discussed locations for inspected/tagged fire extinguishers. Final life fire safety inspection passed/complete.
|
FIR16-00184
| INSP-Final Inspection | 6/20/2016 | 6/20/2016 | 6/20/2016 9:07:11 AM | A | PASS |
|
|
Final fire sprinkler inspection passed/complete
|
FIR15-00808
| INSP-Sprinkler Rough-in/Hydro | 6/17/2016 | 6/20/2016 | 6/20/2016 8:42:57 AM | A | CANC |
|
|
Inspection request re-scheduled per conversation with Mark, phone number ###-#### due to pressure loss for the hydrostatic test.
|
BLD15-04191
| FIRE-Final Inspection | 6/17/2016 | 6/20/2016 | 6/20/2016 8:39:14 AM | A | PART |
|
|
Level 2 fire sprinklers complete, level 2 fire alarms complete, fire extinguishers are in place with cuurent inspection tags for level 2, final life fire safety inspection for level 2 passed/complete.
|