ELE17-01757
| Final | 6/20/2017 | 6/20/2017 | 6/20/2017 2:53:29 PM | P | PASS |
|
|
Final ok
|
ELE17-01757
| Permanent Service | 6/20/2017 | 6/20/2017 | 6/20/2017 2:51:15 PM | P | PASS |
|
|
Service upgrade to 200 amp. p/s o/h rec ok
|
ELE16-03932
| Electrical Rough-In | 6/20/2017 | 6/20/2017 | 6/20/2017 2:42:03 PM | P | PASS |
|
|
units 523 thru 532 Phone #: ###-#### Inspection requested via web by Cathy Duchek Rooms noted and signed in office rough in ok cover
|
ELE17-01336
| Final | 6/20/2017 | 6/20/2017 | 6/20/2017 1:22:01 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by steve ragan 210.8- Break room area all receptacle outlets located with in 6' of a sink shall have GFCI protection. 330.30- All MC cables shall be secured with in 12" of a box and supported at intervals not to exceed 6'.
|
ELE17-01861
| Rough-In Permanent Service | 6/19/2017 | 6/20/2017 | 6/20/2017 12:36:00 PM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by danny perrine 210.52- Up loft receptacles more than 12' apart. Shelving being installed on these walls. 314.17(C)- NM cable sheath shall enter box minimum of 1/4". Smoke by stair. 334.30- MN cable shall be secured with in 12" of a box or stub. Pool wire, AC wire, WP of garage, entry recept., sunroom under window. 422.12- Furnace max amperage 14.8 amp x 125%= 18.5, 20 amp circuit required. 300.4- Nail plates needed where NM cable is run thru bored holes that do not maintain 1 1/4" from framing surface. James said OK to foam seal.
|
ELE17-01698
| Electrical Rough-In | 6/19/2017 | 6/20/2017 | 6/20/2017 12:20:30 PM | A | PASS |
|
|
Wall rough in.
For questions, please speak with Scott Thomas (number provided above)
Thanks... Phone #: ###-#### Inspection requested via web by David Feller Fire alarm boxes located above future hardlid are to be removed and new low volt system being installed. Wall rough in ok cover
|
ELE17-01920
| Rough-In Permanent Service | 6/19/2017 | 6/20/2017 | 6/20/2017 9:53:01 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Alan Lusk Rough in ok cover p/s u/g n ok
|
ELE17-01720
| Rough-In Permanent Service | 6/19/2017 | 6/20/2017 | 6/20/2017 9:17:51 AM | A | PASS |
|
|
The corrections have been completed, TW Phone #: ###-#### Inspection requested via web by Stephen Kren Rough in ok cover p/s u/g n ok 2 meters
|