Inspections for the day of: Tuesday, June 20, 2017.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-01757 Final6/20/20176/20/20176/20/2017 2:53:29 PMPPASS
Final ok
ELE17-01757 Permanent Service6/20/20176/20/20176/20/2017 2:51:15 PMPPASS
Service upgrade to 200 amp.
p/s o/h rec ok
ELE16-03932 Electrical Rough-In6/20/20176/20/20176/20/2017 2:42:03 PMPPASS
units 523 thru 532 Phone #: ###-#### Inspection requested via web by Cathy Duchek
Rooms noted and signed in office rough in ok cover
ELE17-01336 Final6/20/20176/20/20176/20/2017 1:22:01 PMPFAIL
Phone #: ###-#### Inspection requested via web by steve ragan
210.8- Break room area all receptacle outlets located with in 6' of a sink shall have GFCI protection.
330.30- All MC cables shall be secured with in 12" of a box and supported at intervals not to exceed 6'.
ELE17-01861 Rough-In Permanent Service6/19/20176/20/20176/20/2017 12:36:00 PMAFAIL
Phone #: ###-#### Inspection requested via web by danny perrine
210.52- Up loft receptacles more than 12' apart. Shelving being installed on these walls.
314.17(C)- NM cable sheath shall enter box minimum of 1/4". Smoke by stair.
334.30- MN cable shall be secured with in 12" of a box or stub. Pool wire, AC wire, WP of garage, entry recept., sunroom under window.
422.12- Furnace max amperage 14.8 amp x 125%= 18.5, 20 amp circuit required.
300.4- Nail plates needed where NM cable is run thru bored holes that do not maintain 1 1/4" from framing surface.
James said OK to foam seal.
ELE17-01698 Electrical Rough-In6/19/20176/20/20176/20/2017 12:20:30 PMAPASS
Wall rough in.

For questions, please speak with Scott Thomas (number provided above)

Thanks... Phone #: ###-#### Inspection requested via web by David Feller
Fire alarm boxes located above future hardlid are to be removed and new low volt system being installed. Wall rough in ok cover
ELE17-01920 Rough-In Permanent Service6/19/20176/20/20176/20/2017 9:53:01 AMAPASS
Phone #: ###-#### Inspection requested via web by Alan Lusk
Rough in ok cover p/s u/g n ok
ELE17-01720 Rough-In Permanent Service6/19/20176/20/20176/20/2017 9:17:51 AMAPASS
The corrections have been completed, TW Phone #: ###-#### Inspection requested via web by Stephen Kren
Rough in ok cover p/s u/g n ok 2 meters