Inspections for the day of: Wednesday, June 20, 2018.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTom Saunders
TitleELE-INSPECTOR
Phone #208-794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE14-00556 ELE-Aging Inspection6/20/20186/20/20186/22/2018 2:26:56 PM FAIL
contractor making no attempt to schedule or attend to corrections
ELE18-01468 Final6/20/20186/20/20186/20/2018 2:31:20 PMPFAIL
access 2758 Phone #: ###-#### Inspection requested via web by David Nelson...
1) all outlets serving kitchen counters shall have GFCI protection...210.8(A)...outlet labelled micro in panel
2) boxes set back in combustible material shall extend to finished surface...314.20...dining rm
ELE18-00526 Final6/20/20186/20/20186/20/2018 12:31:30 PMPFAIL
Dan Phone #: ###-####...
1) no power in washer outlet..110.7
2) outlet in laundery room needs changed...new outlet and plate...110.3
3) missing switch plate in master closet...110.3
4) master closet light to close to shelving...410.16
5) closet light to close to shelving..ent. rm...410.16
ELE18-00535 Final6/19/20186/20/20186/20/2018 10:35:00 AMAPASS
Please call when in route. Phone #: ###-#### Inspection requested via web by Spencer McLean...job complete...labelling and disconnect ok to final
ELE18-00966 Final6/19/20186/20/20186/20/2018 10:11:21 AMAPART
Max Phone #: ###-####...partial final for new offices, bathrooms, and breakroom so staff may move in...remaining work is demo on existing building and new entry once built...can in soffit and outlet
ELE18-02206 Permanent Service6/20/20186/20/20186/20/2018 9:36:09 AMAPASS
p/s o/h reconnect ok
ELE18-02206 Final6/19/20186/20/20186/20/2018 9:28:04 AMAPASS
Roger Phone #: ###-####...p/s o/h reconnect ok
ELE18-00999 Final6/20/20186/20/20186/20/2018 9:07:51 AMAPASS
ok to final
ELE18-00860 Electrical Rough-In6/19/20186/20/20186/20/2018 9:06:32 AMAPASS
Phone #: ###-#### Inspection requested via web by Justin Hone...stage one...new laundry and family rm...rough ok to cover
ELE18-02274 Electrical Rough-In6/20/20186/20/20186/20/2018 8:42:19 AMAPASS
Underground Phone #: ###-#### Inspection requested via web by Jason Wicks....underground for first 6...ok to cover
ELE18-02275 Temporary Service6/19/20186/20/20186/19/2018 2:54:08 PMAPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn...
t/s u/g new ok
ELE18-02276 Temporary Service6/19/20186/20/20186/19/2018 2:53:18 PMAPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn...t/s u/g new ok