MEC19-02642
| Final | 6/20/2019 | 6/20/2019 | 6/20/2019 4:23:57 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Floyd Floyd Peek - water heater flue needs 6" clearances from new line set - several locations on line set insulation need rips fixed
|
MEC19-02453
| Rough-in | 6/19/2019 | 6/20/2019 | 6/20/2019 3:07:13 PM | P | FAIL |
|
|
Antonio is the contact Phone #: ###-#### Inspection requested via web by stan lillquist - few areas need duct sealed finished above ceiling - duct work above ceiling will need insulated after being sealed - venting for dryer system needs installed and I will need manufactures installation instructions onsite at time of inspection
|
MEC19-02453
| Final | 6/19/2019 | 6/20/2019 | 6/20/2019 3:04:36 PM | P | NR |
|
|
Antonio is the contact Phone #: ###-#### Inspection requested via web by stan lillquist
|
MEC19-01777
| Rough-in | 6/20/2019 | 6/20/2019 | 6/20/2019 2:34:41 PM | P | FAIL |
|
|
cover inspection Phone #: ###-#### Inspection requested via web by Brandon - duct smoke detectors ok - ductless split condensate needs to be ran in min 3/4" approved material. Use pump to achieve grade then gravity drain in approved material
|
MEC19-02471
| Final | 6/18/2019 | 6/20/2019 | 6/20/2019 2:28:58 PM | P | FAIL |
|
|
Please have inspector call owner Susie when in route to home at ###-#### Phone #: ###-#### Inspection requested via web by Carolyn Rudd - need to witness a 5lb flue pressure test on furnace - line set penetration needs sealed
|
MEC19-02486
| Final | 6/13/2019 | 6/20/2019 | 6/20/2019 2:09:24 PM | P | FAIL |
|
|
INSTALLER GERRY ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt - no access to roof for RTU final inspection. Reschedule inspection with access to roof
|
MEC19-02455
| Final | 6/14/2019 | 6/20/2019 | 6/20/2019 1:51:11 PM | P | PASS |
|
|
Homeowner requests 1-4pm Phone #: ###-#### Inspection requested via web by Michael Stimpson - A/C coil co ok
|
MEC19-02571
| Final | 6/18/2019 | 6/20/2019 | 6/20/2019 1:32:33 PM | P | NH |
|
|
If possible, please call home owner one hour before at ###-####. She works an hour away. Thank you. Phone #: ###-#### Inspection requested via web by James Cox - no access to home left notice on front door
|
MEC19-02551
| Final | 6/19/2019 | 6/20/2019 | 6/20/2019 10:23:51 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Marisa Hone - furnace ac coil co ok
|
MEC19-02390
| Final | 6/18/2019 | 6/20/2019 | 6/20/2019 9:54:59 AM | A | FAIL |
|
|
Please call Leslie at ###-#### on your way. Thanks! Phone #: ###-#### Inspection requested via web by Misty Merry - A/C fuse size is too large - need to finish taping cut in line set insulation
|
MEC19-01120
| Final | 6/14/2019 | 6/20/2019 | 6/20/2019 9:31:06 AM | A | PASS |
|
|
CASEY ###-#### Phone #: ###-#### Inspection requested via web by Mike Almanza - fireplace final ok
|
MEC19-02608
| Final | 6/18/2019 | 6/20/2019 | 6/20/2019 9:19:02 AM | A | FAIL |
|
|
Contact Carey ###-#### Phone #: ###-#### Inspection requested via web by John Bertram - A/C fuses sizes are too big - gas lines for both water heater and furnace need sediment traps - common vent needs to be a wye and needs re configured where the smallest connector enters at the highest level
|
MEC18-05355
| Mec-Aging Inspection | 6/20/2019 | 6/20/2019 | 6/20/2019 8:27:38 AM | | FAIL |
|
|
need to schedule inspection with homeowner to check corrections. Permit has not been active since the failed inspection.
|
MEC18-03214
| Mec-Aging Inspection | 6/20/2019 | 6/20/2019 | 6/20/2019 8:26:14 AM | | PASS |
|
|
No contact with the homeowner has been after leaving two notices at location. Permit expired
|
MEC18-03214
| DOC - Permit Expired | 6/20/2019 | 6/20/2019 | 6/20/2019 8:25:05 AM | A | PASS |
|
|
expire permit ok
|
MEC19-01592
| Final | 6/19/2019 | 6/20/2019 | 6/19/2019 2:43:43 PM | A | CANC |
|
|
Mechanical Gas fireplace Final inspection Please call Dane @ ###-#### when headed that way. Phone #: ###-#### >> Inspection requested via web by Dan Otero Inspection cancelled from web by: Dan Otero
|