BLD02-00477
| FIRE-Final Inspection | 6/21/2002 | 6/21/2002 | 6/21/2002 12:00:00 AM | A | FAIL |
|
|
Scheduled by Inspector: 409 On 6/21/2002 8:45:54 AM occupant load sign; south exit door not installed; sprinkler heads painted; couldn't complete alarm test - no power to AHU's 6/21/2002 8:49:07 AM
|
FIR02-00177
| INSP-Final Inspection | 6/21/2002 | 6/21/2002 | 6/21/2002 12:00:00 AM | A | FAIL |
|
|
Scheduled by Inspector: 409 On 6/21/2002 8:46:44 AM sprinkler heads has tape on it; head painted above food prep area 6/21/2002 8:49:33 AM
|
FIR02-00194
| INSP-Final Inspection | 6/21/2002 | 6/21/2002 | 6/21/2002 12:00:00 AM | A | FAIL |
|
|
Scheduled by Inspector: 409 On 6/21/2002 8:47:31 AM no power to AHU's so couldn't test duct detectors for shut down of units 6/21/2002 8:50:08 AM
|
FIR02-00240
| INSP-Final Inspection | 6/21/2002 | 6/21/2002 | 6/21/2002 12:00:00 AM | A | FAIL |
|
|
Scheduled by Inspector: 409 On 6/21/2002 9:21:12 AM inspection conducted at 1:30 - 2:30 am; additional inspection fee info provided to Linda H. In-duct detector not working for damper; requires reinspection 6/21/2002 9:23:31 AM
|
FIR02-00130
| INSP-Sprinkler Rough-in/Hydro | 6/19/2002 | 6/21/2002 | 6/21/2002 12:00:00 AM | A | CANC |
|
|
Scheduled by a contractor via Hello! on 06/19/2002 at 16:33:59. Contact: ###-####. I ran out of time today; will reschedule for 6/24 6/21/2002 4:02:38 PM
|
BLD01-01469
| FIRE-Final Inspection | 6/20/2002 | 6/21/2002 | 6/21/2002 12:00:00 AM | P | FAIL |
|
|
Scheduled by Inspector: 409 On 6/20/2002 11:07:42 AM curbing for fire lanes; alarm account active; ball drip for sprinkler FDC to outside; complete one hour riser room; keys for knox box; sign on door to riser room indicating sprinkler controls and FACP 6/21/2002 3:55:48 PM
|
FIR01-00425
| INSP-Final Inspection | 6/21/2002 | 6/21/2002 | 6/21/2002 12:00:00 AM | P | FAIL |
|
|
Scheduled by Inspector: 409 On 6/21/2002 12:59:42 PM need account active 6/21/2002 3:54:05 PM
|
FIR01-00524
| INSP-Final Inspection | 6/21/2002 | 6/21/2002 | 6/21/2002 12:00:00 AM | P | FAIL |
|
|
Scheduled by Inspector: 409 On 6/21/2002 1:00:06 PM need ball drip to outside; need fire marshall tag 6/21/2002 3:53:31 PM
|
BLD02-00978
| FIRE-Sprinkler Rough-in | 6/21/2002 | 6/21/2002 | 6/21/2002 12:00:00 AM | P | PASS |
|
|
Added by Inspector: 409 On 6/21/2002 3:43:34 PM okay to cover
|
BLD02-01037
| FIRE-Final Inspection | 6/21/2002 | 6/21/2002 | 6/21/2002 12:00:00 AM | P | PASS |
|
|
Scheduled by Inspector: 409 On 6/21/2002 4:12:27 PM
|
FIR02-00240
| INSP-Final Inspection | 6/21/2002 | 6/21/2002 | 6/21/2002 12:00:00 AM | P | PASS |
|
|
Added by Inspector: 409 On 6/21/2002 4:13:11 PM
|
FIR02-00216
| INSP-Final Inspection | 6/21/2002 | 6/21/2002 | 6/21/2002 12:00:00 AM | P | PART |
|
|
###-#### MIKE not a final; okay to cover 6/21/2002 3:43:55 PM
|