FIR03-00269
| FIR-Aging Inspection | 6/21/2005 | 6/21/2005 | 6/24/2005 3:38:45 PM | | DONE |
|
|
Spoke with Rob from Protex at ###-####, he was not sure why this permit is still open. He is to find out and call in for an inspection.
|
FIR03-00134
| FIR-Aging Inspection | 6/21/2005 | 6/21/2005 | 6/24/2005 3:32:52 PM | | PASS |
|
|
Permit finaled. UG hydro done by Troy Cobbley on 7/10/03, UG flush and rough-in done by Rick Jackson on 7/16/03.
|
FIR04-00258
| INSP-Sprinkler Rough-in | 6/20/2005 | 6/21/2005 | 6/21/2005 4:40:12 PM | A | FAIL |
|
|
Heads in four areas as marked on approved plans are blocked and need repositioning, Provide flexible coupling at riser before floor penetration.
|
BLD03-02329
| FIRE-Final Inspection | 6/20/2005 | 6/21/2005 | 6/21/2005 4:35:56 PM | P | CANC |
|
|
Cancel inspection per Burl with AIC, not ready for inspection, waiting on phone lines and smoke detector install.
|
BLD04-02143
| FIRE-Final Inspection | 6/21/2005 | 6/21/2005 | 6/21/2005 2:25:44 PM | P | PASS |
|
|
Fire life safety passed inspection.
|
MIS05-00025
| FIR-Final | 6/21/2005 | 6/21/2005 | 6/21/2005 1:51:33 PM | P | FAIL |
|
|
Remove thumbturn at west door, relocate fire ext. to a normal path of travel, door hardware must be of the approved type.
|
FIR05-00325
| INSP-Final Inspection | 6/20/2005 | 6/21/2005 | 6/21/2005 1:13:51 PM | P | PASS |
|
|
Fire sprinkler passed final inspection.
|
FIR05-00351
| INSP-Sprinkler Rough-in/Hydro | 6/21/2005 | 6/21/2005 | 6/21/2005 12:38:53 PM | A | PART |
|
|
Overhead fire sprinkler rough-in OK for cover.
|
FIR05-00359
| INSP-Final Inspection | 6/20/2005 | 6/21/2005 | 6/21/2005 12:07:58 PM | P | CANC |
|
|
Cancel per contractor, not ready for inspection.
|
BLD05-00523
| FIRE-Final Inspection | 6/20/2005 | 6/21/2005 | 6/21/2005 11:57:27 AM | A | PASS |
|
|
Fire life safety passed inspection.
|
BLD04-02972
| FIRE-Final Inspection | 6/20/2005 | 6/21/2005 | 6/21/2005 11:21:51 AM | A | FAIL |
|
|
Need to provide current annual inspection on fire sprinkler system.
|
BLD05-00291
| FIRE-Final Inspection | 6/20/2005 | 6/21/2005 | 6/21/2005 10:24:00 AM | A | PASS |
|
|
Fire life safety finaled.
|
MIS05-00069
| FIR-Final | 6/17/2005 | 6/21/2005 | 6/21/2005 10:05:25 AM | A | PART |
|
|
Need provision to test emergency light in north stairway.
|
MIS05-00068
| FIR-Final | 6/17/2005 | 6/21/2005 | 6/21/2005 10:02:57 AM | A | FAIL |
|
|
Exit sign at top of stairs in front of Idaho Rivers does not operate under battery backup power.
|
MIS05-00066
| FIR-Final | 6/17/2005 | 6/21/2005 | 6/21/2005 10:00:18 AM | A | PASS |
|
|
Fire life safety finaled.
|
MIS05-00065
| FIR-Final | 6/17/2005 | 6/21/2005 | 6/21/2005 9:59:08 AM | A | PASS |
|
|
Fire life safety passed inspection.
|
BLD04-01051
| FIRE-Final Inspection | 6/21/2005 | 6/21/2005 | 6/21/2005 12:00:00 AM | A | FAIL |
|
|
Duct smoke detectors failed to shut HVAC units off upon activation, exit discharge lighting at three locations still not working, door hardware at two doors is not approved.
|
FIR05-00069
| INSP-Sprinkler Rough-in | 6/21/2005 | 6/21/2005 | 6/21/2005 12:00:00 AM | P | FAIL |
|
|
Provide hanger at 2nd floor arm over greater than 2' in length, add head 2nd floor as shown on plans beyond tenant demising wall.
|