Inspections for the day of: Tuesday, June 21, 2005.
Number of inspections: 18
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR03-00269 FIR-Aging Inspection6/21/20056/21/20056/24/2005 3:38:45 PM DONE
Spoke with Rob from Protex at ###-####, he was not sure why this permit is still open. He is to find out and call in for an inspection.
FIR03-00134 FIR-Aging Inspection6/21/20056/21/20056/24/2005 3:32:52 PM PASS
Permit finaled. UG hydro done by Troy Cobbley on 7/10/03, UG flush and rough-in done by Rick Jackson on 7/16/03.
FIR04-00258 INSP-Sprinkler Rough-in6/20/20056/21/20056/21/2005 4:40:12 PMAFAIL
Heads in four areas as marked on approved plans are blocked and need repositioning, Provide flexible coupling at riser before floor penetration.
BLD03-02329 FIRE-Final Inspection6/20/20056/21/20056/21/2005 4:35:56 PMPCANC
Cancel inspection per Burl with AIC, not ready for inspection, waiting on phone lines and smoke detector install.
BLD04-02143 FIRE-Final Inspection6/21/20056/21/20056/21/2005 2:25:44 PMPPASS
Fire life safety passed inspection.
MIS05-00025 FIR-Final6/21/20056/21/20056/21/2005 1:51:33 PMPFAIL
Remove thumbturn at west door, relocate fire ext. to a normal path of travel, door hardware must be of the approved type.
FIR05-00325 INSP-Final Inspection6/20/20056/21/20056/21/2005 1:13:51 PMPPASS
Fire sprinkler passed final inspection.
FIR05-00351 INSP-Sprinkler Rough-in/Hydro6/21/20056/21/20056/21/2005 12:38:53 PMAPART
Overhead fire sprinkler rough-in OK for cover.
FIR05-00359 INSP-Final Inspection6/20/20056/21/20056/21/2005 12:07:58 PMPCANC
Cancel per contractor, not ready for inspection.
BLD05-00523 FIRE-Final Inspection6/20/20056/21/20056/21/2005 11:57:27 AMAPASS
Fire life safety passed inspection.
BLD04-02972 FIRE-Final Inspection6/20/20056/21/20056/21/2005 11:21:51 AMAFAIL
Need to provide current annual inspection on fire sprinkler system.
BLD05-00291 FIRE-Final Inspection6/20/20056/21/20056/21/2005 10:24:00 AMAPASS
Fire life safety finaled.
MIS05-00069 FIR-Final6/17/20056/21/20056/21/2005 10:05:25 AMAPART
Need provision to test emergency light in north stairway.
MIS05-00068 FIR-Final6/17/20056/21/20056/21/2005 10:02:57 AMAFAIL
Exit sign at top of stairs in front of Idaho Rivers does not operate under battery backup power.
MIS05-00066 FIR-Final6/17/20056/21/20056/21/2005 10:00:18 AMAPASS
Fire life safety finaled.
MIS05-00065 FIR-Final6/17/20056/21/20056/21/2005 9:59:08 AMAPASS
Fire life safety passed inspection.
BLD04-01051 FIRE-Final Inspection6/21/20056/21/20056/21/2005 12:00:00 AMAFAIL
Duct smoke detectors failed to shut HVAC units off upon activation, exit discharge lighting at three locations still not working, door hardware at two doors is not approved.
FIR05-00069 INSP-Sprinkler Rough-in6/21/20056/21/20056/21/2005 12:00:00 AMPFAIL
Provide hanger at 2nd floor arm over greater than 2' in length, add head 2nd floor as shown on plans beyond tenant demising wall.