ELE06-00985
| ELE-Aging Inspection | 6/21/2006 | 6/21/2006 | 6/23/2006 4:45:34 PM | | NR |
|
|
called , they will call next week
|
ELE06-01341
| ELE-Aging Inspection | 6/21/2006 | 6/21/2006 | 6/21/2006 5:13:06 PM | | DONE |
|
|
suc
|
ELE06-00825
| Final | 6/21/2006 | 6/21/2006 | 6/21/2006 4:29:21 PM | P | PASS |
|
|
final on pool thanks joe; Phone #: ###-#### Internet Inspection Request from: joe wheeler called contr about cover, ok to final
|
ELE06-00159
| Final | 6/21/2006 | 6/21/2006 | 6/21/2006 4:20:53 PM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 6/21/2006 at 5:34:37 AM. Contact: ###-####. called, left message, left corr notice, nec 210.52(A) additional recpt shall be added in dr short wall, 210.8(A)(5) basement recpts shall be gfci protected, 314.29 junction boxes shall be accessible(basement heat), 406.4 back recpt shall be securely mounted,BCC no cover shall be done without inspection(basement ceiling for heat for bathroom floors)
|
ELE06-02139
| Final | 6/20/2006 | 6/21/2006 | 6/21/2006 4:07:12 PM | P | PASS |
|
|
We: 1)relocated the existing dryer circuit to the basement, 2)converted the existing range circuit / receptacle to a 120 volt circuit / receptacle.(#6050440/441bw).J-man Jason/###-####. Thanks!!!!!; Phone #: ###-#### Internet Inspection Request from: Dan Mitchell ok to final
|
ELE06-02269
| Final | 6/20/2006 | 6/21/2006 | 6/21/2006 3:12:10 PM | P | PASS |
|
|
Work performed by Tom Wonacott. Gate code #5596; Phone #: ###-#### Internet Inspection Request from: Matt Santacruz ok to final
|
ELE06-01691
| Rough-In Permanent Service | 6/21/2006 | 6/21/2006 | 6/21/2006 2:20:00 PM | P | PASS |
|
|
POTTING INSPECTION CONTACT ###-#### (RIK); Phone #: ###-#### Internet Inspection Request from: Cathy Felin potting ok, NOTE: looked at column bonding before completely decked over, for hot tub and ok
|
ELE06-01731
| Final | 6/21/2006 | 6/21/2006 | 6/21/2006 1:49:49 PM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Shawna Hall called left survey,nec 110.3(B) recpt shall operate in hall and screws installed in one
|
ELE06-01191
| Final | 6/21/2006 | 6/21/2006 | 6/21/2006 1:39:03 PM | P | FAIL |
|
|
shellie ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie called left corr notice,nec 406.5&404.9 faceplates shall seat against finished surface,406.4(D) recpt faces shall be flush with or project from faceplates
|
ELE06-02250
| Rough-In Permanent Service | 6/20/2006 | 6/21/2006 | 6/21/2006 11:35:12 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Joe Thomas corr made, ric ok, p/s u/g n ok
|
ELE06-02230
| Rough-In Permanent Service | 6/20/2006 | 6/21/2006 | 6/21/2006 10:29:40 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 6/20/2006 at 2:52:11 PM. Contact: ###-####. corr made, ric ok, p/s u/g n ok
|
ELE06-02247
| Electrical Rough-In | 6/20/2006 | 6/21/2006 | 6/21/2006 10:07:24 AM | A | PASS |
|
|
reinspection on 1 room rough in. Any Questions call Tate @ ###-#### Internet Inspection Request from: Andy Rose corr made, ric ok
|
ELE06-01834
| Electrical Rough-In | 6/19/2006 | 6/21/2006 | 6/21/2006 9:45:44 AM | A | FAIL |
|
|
victor; Phone #: ###-#### Internet Inspection Request from: Rita DeYoung talked to builder not homeowner,called office, told builder permit voided, since he is not electrician or homeowner. Left corr notice and do not cover sticker, nec 300.4(A)&(D) edge of holes and nm cable shall be 1 1/4" from edge of framing members, 314.20 in walls of combustible material, boxes shall be flush with finished surface or project therefrom, 300.14 at least 6" free conductor shall be at each box,BCC all make-up shall be done
|
ELE06-02229
| Electrical Rough-In | 6/20/2006 | 6/21/2006 | 6/21/2006 8:42:29 AM | A | CANC |
|
|
shelly; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles see rip
|
ELE06-02229
| Rough-In Permanent Service | 6/21/2006 | 6/21/2006 | 6/21/2006 8:42:04 AM | A | PASS |
|
|
shelly; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corr made, ric ok, p/s u/g n ok
|
ELE06-02290
| Rough-In Permanent Service | 6/20/2006 | 6/21/2006 | 6/21/2006 8:13:46 AM | A | FAIL |
|
|
ted; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley called, left message, left corr notice, nec 300.4(A)&(D) edge of holes and nm cable shall be 1 1/4" from edge of framing members, 334.30 nm cable shall be secured within 12" of box
|
ELE06-02229
| Rough-In Permanent Service | 6/21/2006 | 6/21/2006 | 6/21/2006 12:00:00 AM | P | CANC |
|
|
shellie ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie--already set up for am
|
ELE06-02290
| Rough-In Permanent Service | 6/20/2006 | 6/21/2006 | 6/20/2006 4:46:24 PM | A | CANC |
|
|
Phone #: ###-#### Internet Inspection Request from: Shawna Hall Inspection cancelled from web by: Barbara Buckley
|