Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-00985 ELE-Aging Inspection6/21/20066/21/20066/23/2006 4:45:34 PM NR
called , they will call next week
ELE06-01341 ELE-Aging Inspection6/21/20066/21/20066/21/2006 5:13:06 PM DONE
suc
ELE06-00825 Final6/21/20066/21/20066/21/2006 4:29:21 PMPPASS
final on pool thanks joe; Phone #: ###-#### Internet Inspection Request from: joe wheeler called contr about cover, ok to final
ELE06-00159 Final6/21/20066/21/20066/21/2006 4:20:53 PMPFAIL
Scheduled by a contractor via Hello! on 6/21/2006 at 5:34:37 AM. Contact: ###-####. called, left message, left corr notice, nec 210.52(A) additional recpt shall be added in dr short wall, 210.8(A)(5) basement recpts shall be gfci protected, 314.29 junction boxes shall be accessible(basement heat), 406.4 back recpt shall be securely mounted,BCC no cover shall be done without inspection(basement ceiling for heat for bathroom floors)
ELE06-02139 Final6/20/20066/21/20066/21/2006 4:07:12 PMPPASS
We: 1)relocated the existing dryer circuit to the basement, 2)converted the existing range circuit / receptacle to a 120 volt circuit / receptacle.(#6050440/441bw).J-man Jason/###-####. Thanks!!!!!; Phone #: ###-#### Internet Inspection Request from: Dan Mitchell ok to final
ELE06-02269 Final6/20/20066/21/20066/21/2006 3:12:10 PMPPASS
Work performed by Tom Wonacott. Gate code #5596; Phone #: ###-#### Internet Inspection Request from: Matt Santacruz ok to final
ELE06-01691 Rough-In Permanent Service6/21/20066/21/20066/21/2006 2:20:00 PMPPASS
POTTING INSPECTION CONTACT ###-#### (RIK); Phone #: ###-#### Internet Inspection Request from: Cathy Felin potting ok, NOTE: looked at column bonding before completely decked over, for hot tub and ok
ELE06-01731 Final6/21/20066/21/20066/21/2006 1:49:49 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Shawna Hall called left survey,nec 110.3(B) recpt shall operate in hall and screws installed in one
ELE06-01191 Final6/21/20066/21/20066/21/2006 1:39:03 PMPFAIL
shellie ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie called left corr notice,nec 406.5&404.9 faceplates shall seat against finished surface,406.4(D) recpt faces shall be flush with or project from faceplates
ELE06-02250 Rough-In Permanent Service6/20/20066/21/20066/21/2006 11:35:12 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Joe Thomas corr made, ric ok, p/s u/g n ok
ELE06-02230 Rough-In Permanent Service6/20/20066/21/20066/21/2006 10:29:40 AMAPASS
Scheduled by a contractor via Hello! on 6/20/2006 at 2:52:11 PM. Contact: ###-####. corr made, ric ok, p/s u/g n ok
ELE06-02247 Electrical Rough-In6/20/20066/21/20066/21/2006 10:07:24 AMAPASS
reinspection on 1 room rough in. Any Questions call Tate @ ###-#### Internet Inspection Request from: Andy Rose corr made, ric ok
ELE06-01834 Electrical Rough-In6/19/20066/21/20066/21/2006 9:45:44 AMAFAIL
victor; Phone #: ###-#### Internet Inspection Request from: Rita DeYoung talked to builder not homeowner,called office, told builder permit voided, since he is not electrician or homeowner. Left corr notice and do not cover sticker, nec 300.4(A)&(D) edge of holes and nm cable shall be 1 1/4" from edge of framing members, 314.20 in walls of combustible material, boxes shall be flush with finished surface or project therefrom, 300.14 at least 6" free conductor shall be at each box,BCC all make-up shall be done
ELE06-02229 Electrical Rough-In6/20/20066/21/20066/21/2006 8:42:29 AMACANC
shelly; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles see rip
ELE06-02229 Rough-In Permanent Service6/21/20066/21/20066/21/2006 8:42:04 AMAPASS
shelly; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corr made, ric ok, p/s u/g n ok
ELE06-02290 Rough-In Permanent Service6/20/20066/21/20066/21/2006 8:13:46 AMAFAIL
ted; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley called, left message, left corr notice, nec 300.4(A)&(D) edge of holes and nm cable shall be 1 1/4" from edge of framing members, 334.30 nm cable shall be secured within 12" of box
ELE06-02229 Rough-In Permanent Service6/21/20066/21/20066/21/2006 12:00:00 AMPCANC
shellie ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie--already set up for am
ELE06-02290 Rough-In Permanent Service6/20/20066/21/20066/20/2006 4:46:24 PMACANC
Phone #: ###-#### Internet Inspection Request from: Shawna Hall Inspection cancelled from web by: Barbara Buckley