Inspections for the day of: Wednesday, June 21, 2006.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00801 FIR-Aging Inspection6/21/20066/21/20066/23/2006 2:01:25 PM NR
Central tower work is in progress
FIR06-00058 INSP-Final Inspection6/21/20066/21/20066/21/2006 5:24:44 PMPFAIL
Provide separate point for the tamper and low air on the dry pipe valve. Need to verify all signals.
FIR06-00200 INSP-Sprinkler Rough-in/Hydro6/20/20066/21/20066/21/2006 3:40:56 PMAPART
Above ground hydro test passed but the forward flush failed.
BLD06-01172 FIRE-Final Inspection6/20/20066/21/20066/21/2006 1:49:18 PMAFAIL
Provide approved door hardware on all the exterior doors as per the door schedule. Remove the manual flush bolts from the inner double doors at the north end. Provide seven exit/emergency lights as marked on the approved plans and lower the two fire extinguishers.
FIR06-00327 INSP-Sprinkler Rough-in/Hydro6/20/20066/21/20066/21/2006 1:30:06 PMAPASS
Sprinkler piping is ok to cover.
FIR06-00317 INSP-Final Inspection6/20/20066/21/20066/21/2006 11:51:49 AMAFAIL
Strobes are mounted too low and candella is wrong. See plans for locations.
FIR06-00194 INSP-Final Inspection6/20/20066/21/20066/21/2006 11:51:08 AMAFAIL
Need gas for the hvac units to verify shutdown and the nfpa 72 record of completion forms. All other items including signals passed.
BLD06-01380 FIRE-Final Inspection6/20/20066/21/20066/21/2006 9:33:53 AMAPASS
Life safety finaled
FIR06-00068 INSP-Final Inspection6/20/20066/21/20066/21/2006 9:13:55 AMAFAIL
Need to do forward flush, repair flow switch on the wet riser, provide inspection tags and hydraulic stickers on the dry riser. Also the review comments need verified for any other items that may be listed.
BLD05-02585 FIRE-Final Inspection6/20/20066/21/20066/20/2006 3:33:15 PMAPASS
life safety finaled