Inspections for the day of: Thursday, June 21, 2007.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-00492 INSP-Alarm Testing6/20/20076/21/20076/22/2007 2:59:23 PMPCANC
Contractor and I could not get time corrdinated to meet for inspection. To be rescheduled.
FIR07-00378 INSP-Final Inspection6/20/20076/21/20076/21/2007 12:47:06 PMPFAIL
the smoke detectors outside of the restroom. The devices at the main entrance tested ok but the devices at the nurses station will need to be tested when the two smoke detectors are relocated.
FIR07-00476 INSP-Final Inspection6/20/20076/21/20076/21/2007 11:57:02 AMPPASS
permit finaled. The horn in the storage room, just off of the laundry room was not temporal in sound and was corrected as I waited
BLD07-00706 FIRE-Conference6/20/20076/21/20076/21/2007 10:08:43 AMADONE
The new room is going to be used for storage and the existing sprinkler pendants appear to be overspaced. I explained to the contractor that a separate permit will be required
FIR07-00426 INSP-Sprinkler Rough-in6/20/20076/21/20076/21/2007 9:08:18 AMAPASS
sprinkler piping is ok to cover