Inspections for the day of: Tuesday, June 21, 2011.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE11-01292 Electrical Rough-In6/21/20116/21/20116/21/2011 3:23:11 PMPPASS
Please perform an Electrical Rough-In. Our Contact on-site is Kyle Sharp at ###-####. Thank you. Phone #: ###-#### >> Inspection requested via web by Clint Tate
ok walls
ELE10-00672 Extend Permit 180 days6/21/20116/21/20116/21/2011 3:22:47 PMPPASS
ok for extension called owner
ELE11-00609 Electrical Rough-In6/21/20116/21/20116/21/2011 3:22:29 PMPPART
jason Phone #: ###-#### grid ceiling 1st floor grid line (E) north
ELE11-00856 Electrical Rough-In6/21/20116/21/20116/21/2011 3:21:18 PMPPART
ok
ELE11-01030 Final6/21/20116/21/20116/21/2011 3:20:54 PMPPASS
retro fit fixtures
ELE11-01289 Final6/21/20116/21/20116/21/2011 2:01:22 PMPPASS
ok could not lock door need key
ELE11-01289 Permanent Service6/21/20116/21/20116/21/2011 2:00:43 PMPPASS
This home has been without power for over a year, IP is requiring an insp. before powering, the front door is unlocked due to the key box is broken, please lock it when done, thanks! TW. Phone #: ###-#### >> Inspection requested via web by Stephen Kren
p/s u/g rec. ok
ELE11-01193 Final6/21/20116/21/20116/21/2011 1:58:17 PMPPASS
Jeremy Phone #: ###-#### ok card signed
ELE10-00672 ELE-Aging Inspection6/21/20116/21/20116/21/2011 12:23:16 PM DONE
see added extension
ELE11-01274 Permanent Service6/21/20116/21/20116/21/2011 12:19:03 PMPPASS
p/s u/g new ok
ELE11-01285 Temporary Service6/20/20116/21/20116/21/2011 11:45:26 AMAFAIL
Call 20min prior-- Ferdi Phone #: ###-#### called250.24 (A)(1) terminate GEC to neutral bus with neutral 250.64(E) use kisted metallic conn. for GEC or use plastic, 250.53(G) drive grd rod flush
ELE11-01183 Electrical Rough-In6/20/20116/21/20116/21/2011 11:37:48 AMAPASS
Jon Electrical Underground Phone #: ###-#### >> Inspection requested via web by Sean DeLacy ok
ELE11-01245 Electrical Rough-In6/20/20116/21/20116/21/2011 11:37:28 AMAPASS
Contact: Shon Crabtree Phone #: ###-#### >> Inspection requested via web by Deb Gooden walls 4 rms ok
GCE11-00046 GCE-Permanent Service6/20/20116/21/20116/21/2011 10:43:09 AMAFAIL
Perm ServiceTodd @ ###-####Call in advance - AM Inspection myers hubs not listed for grding or bonding needs #1/0 for water, and service grds and bond 250.66 T, needs grounded conductor brought to service dissconnect note transfer switch suzi rated for normal power
ELE11-01301 Electrical Rough-In6/21/20116/21/20116/21/2011 8:57:38 AMAFAIL
a/c called needs gfci recept within 25ft
ELE11-01301 Final6/20/20116/21/20116/21/2011 8:56:51 AMAFAIL
Cal Phone #: ###-#### >> Inspection requested via web by cal crosby see added r/i