Inspections for the day of: Thursday, June 21, 2012.
Number of inspections: 4
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD12-01294 FIRE-Final Inspection6/21/20126/21/20126/22/2012 3:42:41 PMPFAIL
The walls and ceiling system are still installed. Per Tim in plan review the approved plans, which are not on site, show all of these items to be removed. The space needs to match the plans or plan modifications need to be submitted showing these items to remain. I did test the smoke evac system which functioned correctly.
FIR12-00205 INSP-Sprinkler Rough-in6/20/20126/21/20126/21/2012 2:34:58 PMAPASS
Underground rough in inspection for the riser stub out is passed.
FIR12-00161 INSP-Final Inspection6/20/20126/21/20126/21/2012 2:31:02 PMAFAIL
Inspection turned into a conference. Tom and I walked the project and discussed the obstructions to the pendant sprinkler heads. Some heads have been relocated but other are still blocked by the light fixtures. There is also an issue with esch. on some of the dry sidewalls due to the rock facing not allowing the installation of the canopies.
BLD11-02842 FIRE-Final Inspection6/20/20126/21/20126/21/2012 12:00:00 AMACANC