ELE16-01946
| Conference | 6/21/2016 | 6/21/2016 | 6/21/2016 3:28:29 PM | P | DONE |
|
|
Please call 30 minutes prior Phone #: ###-#### Inspection requested via web by Kerri Hamilton Discussed the location of fire pump at an interior room. This pump shown supplied by seperate service. As per 230.6(2) service entrance conductors shall be concidered outside building, when run inside building it shall be encased by min of 2" of concrete or brick.
|
ELE16-00616
| Final | 6/21/2016 | 6/21/2016 | 6/21/2016 3:16:05 PM | P | PASS |
|
|
Service final ok
|
ELE16-01950
| Final | 6/21/2016 | 6/21/2016 | 6/21/2016 3:15:09 PM | P | PASS |
|
|
Inspection done under permit ELE16-00222. Final ok
|
ELE16-01628
| Conference | 6/21/2016 | 6/21/2016 | 6/21/2016 2:51:18 PM | P | DONE |
|
|
Discussed clearance on HVAC unit disconnecting means and control box. As per Daryl Degrange 24" needed 18" min when no other options exist.
|
ELE13-01291
| Electrical Rough-In | 6/21/2016 | 6/21/2016 | 6/21/2016 2:07:33 PM | P | PASS |
|
|
event lawn underground inspection on site. call Frank Phone #: ###-#### Inspection requested via web by Brandon Robinson South central from electrical room underground rough in ok cover
|
ELE16-00329
| Electrical Rough-In | 6/21/2016 | 6/21/2016 | 6/21/2016 1:25:18 PM | P | PASS |
|
|
Basement ; Formers Phone #: ###-#### Inspection requested via web by Kerri Hamilton Basement GFCI 6' sink, 1st transformers, museum grid, Listed furniture. Basement final ok
|
ELE16-01943
| Electrical Rough-In | 6/20/2016 | 6/21/2016 | 6/21/2016 10:22:50 AM | A | PART |
|
|
Phone #: ###-#### Inspection requested via web by Jim Williams All wall accept s.w. room rough in ok cover
|
ELE16-00257
| Permanent Service | 6/20/2016 | 6/21/2016 | 6/21/2016 9:50:11 AM | A | PASS |
|
|
Mark Phone #: ###-#### p/s o/h n ok
|
ELE16-01934
| Electrical Rough-In | 6/20/2016 | 6/21/2016 | 6/21/2016 9:09:00 AM | A | PASS |
|
|
Trench inspection Phone #: ###-#### Inspection requested via web by steve ragan Back corners of lot rough in ok cover
|