Inspections for the day of: Tuesday, June 21, 2016.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Little
TitlePLM-INSPECTOR
Phone #869-5166
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
PLM16-02215 Final6/20/20166/21/20166/21/2016 2:31:53 PMPFAIL
LOCK BOX CODE 23579 Phone #: ###-#### Inspection requested via web by Jeffrey Hankins
>only one gas flex connector per appliance, you cannot hook two together. per IRC 2422.1.2.1
>leak at cold water flex
PLM15-03019 PLM-Aging Inspection6/21/20166/21/20166/21/2016 2:02:36 PM FAIL
PLM16-02219 Plumbing Rough-in6/21/20166/21/20166/21/2016 1:34:36 PMPPASS
Cory is the project manager ###-####. thank you! Phone #: ###-#### Inspection requested via web by KEVIN FRANKLIN
PLM16-00795 Final6/20/20166/21/20166/21/2016 11:18:01 AMAPASS
Garage code 0505 or 1234 Phone #: ###-#### Inspection requested via web by Semsudin Konjuhovac
PLM16-00461 Final6/20/20166/21/20166/21/2016 10:39:20 AMAFAIL
Phone #: ###-#### Inspection requested via web by Raul Castanon
>Support expansion tank at water heater per,
>313.2-piping shall not be under stress or strain.
>314.5-fixtures, appliances, etc, shall be adequately supported.
PLM16-00461 Water and/or Sewer6/20/20166/21/20166/21/2016 10:37:01 AMACANC
Phone #: ###-#### Inspection requested via web by Raul Castanon
PLM16-00359 Final6/20/20166/21/20166/21/2016 10:13:13 AMAPART
JUSTIN IS THE JOB CONTACT ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER
>floors 2,1 and basement ok
>need to certify DCVA on building main and bypass.
PLM16-02124 Final6/17/20166/21/20166/21/2016 9:11:28 AMAPASS
I have scheduled a mechanical final from 9:30 - 10 AM so our installer can meet the inspector. If at all possible, please inspect in that time frame also, as the homeowner''s son is waiting to go to work until after inspections are done. Phone #: ###-#### Inspection requested via web by Mary LaFayette
>wh ok