Inspections for the day of: Wednesday, June 22, 2005.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-02126 Rough-In Permanent Service6/22/20056/22/20056/22/2005 3:34:06 PMPPART
Scheduled by a contractor via Hello! on 6/22/2005 at 10:01:40 AM. Contact: ###-####. r/i ok cor. posted for p/s called left message, 250.92(A)(3) remove branch circuit from raceway for GEC and bond both ends
ELE05-02152 Permanent Service6/22/20056/22/20056/22/2005 2:57:12 PMPFAIL
###-#### - jeff cor. posted called, all prior violation posted in 2002 permit # ele02-01802 shall be corrected before power is reconnected, 110.26(F)(2) dedicated space for p/s, 250.8 no sheet metal screws for grds or bonds, 230.28 guy kit for mast, 250.52(A)(1) and 250.104(A)(1) grd or bond water system, B.C.C. shall uncover all wiring done without permit or inspections
ELE05-01596 Electrical Rough-In6/22/20056/22/20056/22/2005 2:05:01 PMPPART
Scheduled by a contractor via Hello! on 6/22/2005 at 6:42:40 AM. Contact: ###-####. u/g ok
ELE05-00732 Conference6/22/20056/22/20056/22/2005 1:22:17 PMPPART
richard; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
01 ok
ELE05-01848 Final6/22/20056/22/20056/22/2005 12:48:03 PMPCANC
harvey Note: outside partial wall inspection and incase grounding in concrete; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles needed r/i
ELE04-01825 Final6/22/20056/22/20056/22/2005 12:08:32 PMPPASS
mike --call 1st for access ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie cor. made final ok no card
ELE04-03054 Permanent Service6/21/20056/22/20056/22/2005 10:10:20 AMAPASS
INSPECT SWITCH GEAR PLEASE; Phone #: ###-#### Internet Inspection Request from: Barry Kendall p/s u/g new ok
ELE05-00271 Final6/21/20056/22/20056/22/2005 9:37:58 AMAPASS
###-#### - jerry Please call 1/2 hr prior to inspection final ok cor. made
ELE05-02198 Rough-In Permanent Service6/21/20056/22/20056/22/2005 9:08:57 AMAPART
jack or ###-#### larry; Phone #: ###-#### Internet Inspection Request from: Barbara Moore r/i for house ok no p/s needs clearence 110.26(F)(1)
ELE05-01848 Electrical Rough-In6/22/20056/22/20056/22/2005 12:00:00 AMPPART
harvey Note: outside partial wall inspection and incase grounding in concrete; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles electrode ok for dirt, and exterior walls ok only