FIR05-00311
| INSP-Final Inspection | 6/21/2005 | 6/22/2005 | 6/22/2005 5:42:31 PM | P | PASS |
|
|
Fire alarm passed inspection.
|
BLD04-01882
| FIRE-Final Inspection | 6/22/2005 | 6/22/2005 | 6/22/2005 5:40:49 PM | P | FAIL |
|
|
HVAC RTU at northeast corner of building failed to shut down upon smoke detection, all remaining life safety issues are satisfactory.
|
BLD04-01051
| FIRE-Final Inspection | 6/22/2005 | 6/22/2005 | 6/22/2005 5:32:36 PM | P | FAIL |
|
|
HVAC RTU at northeast corner of building failed to shut down upon smoke detection, all remaining life safety issues are satisfactory.
|
FIR05-00339
| INSP-Final Inspection | 6/21/2005 | 6/22/2005 | 6/22/2005 4:22:28 PM | P | PASS |
|
|
Fire alarm passed inspection.
|
FIR05-00355
| INSP-Sprinkler Rough-in | 6/22/2005 | 6/22/2005 | 6/22/2005 4:16:34 PM | P | PART |
|
|
Ductile iron riser piece and 8' stub out good for cover.
|
FIR05-00341
| INSP-Final Inspection | 6/21/2005 | 6/22/2005 | 6/22/2005 3:01:38 PM | P | PASS |
|
|
Fire alarm finaled.
|
FIR03-00743
| INSP-Final Inspection | 6/21/2005 | 6/22/2005 | 6/22/2005 2:20:06 PM | A | PASS |
|
|
Fire alarm finaled.
|
FIR05-00359
| INSP-Final Inspection | 6/22/2005 | 6/22/2005 | 6/22/2005 12:37:44 PM | P | PART |
|
|
Hood supression system operated properly under test conditions. Cooking appliances not installed yet for verification of placement, class K fire ext. is provided but not mounted.
|
FIR05-00265
| INSP-Sprinkler Rough-in | 6/21/2005 | 6/22/2005 | 6/22/2005 11:35:55 AM | A | FAIL |
|
|
Fail, underground pipe has been buried prior to inspection for cover. Expose pipe and call for a re-inspect.
|
BLD04-01363
| FIRE-Final Inspection | 6/21/2005 | 6/22/2005 | 6/22/2005 11:25:27 AM | A | PASS |
|
|
Fire life safety passed inspection, thumbturn bolt lock at door to new office was removed during inspection.
|
FIR04-00358
| INSP-Final Inspection | 6/21/2005 | 6/22/2005 | 6/22/2005 10:06:35 AM | A | PART |
|
|
Final pending inspection of heads in one room at the basement level to which access was denied, also need to provide seismic clearance at the underground supply where it passes through the foundation wall.
|
BLD04-02590
| FIRE-Final Inspection | 6/21/2005 | 6/22/2005 | 6/22/2005 9:58:30 AM | A | CANC |
|
|
Cancel per Chris at ###-####, no fire permit on this job, inspection was intended for Jim Sly.
|
FIR05-00318
| INSP-Final Inspection | 6/21/2005 | 6/22/2005 | 6/22/2005 8:44:40 AM | A | PASS |
|
|
Fire alarm finaled.
|
FIR05-00234
| INSP-Final Inspection | 6/22/2005 | 6/22/2005 | 6/22/2005 12:00:00 AM | P | PASS |
|
|
Fire sprinkler finaled.
|
FIR05-00307
| INSP-Final Inspection | 6/22/2005 | 6/22/2005 | 6/22/2005 12:00:00 AM | P | PART |
|
|
Hood supression system operated correctly under test conditions. Final pending air balance reports and installation of a class K fire ext. within allowable travel distance.
|