Inspections for the day of: Wednesday, June 22, 2005.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00311 INSP-Final Inspection6/21/20056/22/20056/22/2005 5:42:31 PMPPASS
Fire alarm passed inspection.
BLD04-01882 FIRE-Final Inspection6/22/20056/22/20056/22/2005 5:40:49 PMPFAIL
HVAC RTU at northeast corner of building failed to shut down upon smoke detection, all remaining life safety issues are satisfactory.
BLD04-01051 FIRE-Final Inspection6/22/20056/22/20056/22/2005 5:32:36 PMPFAIL
HVAC RTU at northeast corner of building failed to shut down upon smoke detection, all remaining life safety issues are satisfactory.
FIR05-00339 INSP-Final Inspection6/21/20056/22/20056/22/2005 4:22:28 PMPPASS
Fire alarm passed inspection.
FIR05-00355 INSP-Sprinkler Rough-in6/22/20056/22/20056/22/2005 4:16:34 PMPPART
Ductile iron riser piece and 8' stub out good for cover.
FIR05-00341 INSP-Final Inspection6/21/20056/22/20056/22/2005 3:01:38 PMPPASS
Fire alarm finaled.
FIR03-00743 INSP-Final Inspection6/21/20056/22/20056/22/2005 2:20:06 PMAPASS
Fire alarm finaled.
FIR05-00359 INSP-Final Inspection6/22/20056/22/20056/22/2005 12:37:44 PMPPART
Hood supression system operated properly under test conditions. Cooking appliances not installed yet for verification of placement, class K fire ext. is provided but not mounted.
FIR05-00265 INSP-Sprinkler Rough-in6/21/20056/22/20056/22/2005 11:35:55 AMAFAIL
Fail, underground pipe has been buried prior to inspection for cover. Expose pipe and call for a re-inspect.
BLD04-01363 FIRE-Final Inspection6/21/20056/22/20056/22/2005 11:25:27 AMAPASS
Fire life safety passed inspection, thumbturn bolt lock at door to new office was removed during inspection.
FIR04-00358 INSP-Final Inspection6/21/20056/22/20056/22/2005 10:06:35 AMAPART
Final pending inspection of heads in one room at the basement level to which access was denied, also need to provide seismic clearance at the underground supply where it passes through the foundation wall.
BLD04-02590 FIRE-Final Inspection6/21/20056/22/20056/22/2005 9:58:30 AMACANC
Cancel per Chris at ###-####, no fire permit on this job, inspection was intended for Jim Sly.
FIR05-00318 INSP-Final Inspection6/21/20056/22/20056/22/2005 8:44:40 AMAPASS
Fire alarm finaled.
FIR05-00234 INSP-Final Inspection6/22/20056/22/20056/22/2005 12:00:00 AMPPASS
Fire sprinkler finaled.
FIR05-00307 INSP-Final Inspection6/22/20056/22/20056/22/2005 12:00:00 AMPPART
Hood supression system operated correctly under test conditions. Final pending air balance reports and installation of a class K fire ext. within allowable travel distance.