Inspections for the day of: Friday, June 22, 2007.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-00205 INSP-Sprinkler Rough-in6/21/20076/22/20076/22/2007 5:49:39 PMPFAIL
Completed rough-in inspection for the basement subfab, process bay and chem. labs per sheet FP3, noted locations where head spacing, seismic bracing, and hangers need to be corrected, circled areas where install is not complete.
FIR06-00940 INSP-Sprinkler Rough-in6/21/20076/22/20076/22/2007 5:41:12 PMAFAIL
Plans do not match install.
BLD06-00875 FIRE-Final Inspection6/22/20076/22/20076/22/2007 2:44:16 PMPPASS
Corrections verified for completion, no signature card available on site.
FIR07-00357 INSP-Sprinkler Rough-in6/22/20076/22/20076/22/2007 2:25:40 PMPFAIL
Wrong permit number requested for inspection, apparently was intended for FIR07-00270 which failed due to plans not matching installation.
BLD06-02135 FIRE-Final Inspection6/22/20076/22/20076/22/2007 2:23:24 PMPFAIL
Missing the required fire extinguisher.
FIR06-00540 INSP-Sprinkler Rough-in/Hydro6/21/20076/22/20076/22/2007 12:35:20 PMAPART
OH rough-in inspection for the 1st floor NW quad, noted three retaining straps not attatched to the beam, one pendent head in the men's restroom needs adjustment, heads at some locations are not yet cut into the ceiling tile. Also completed cursory walk through of a tenant improvement on the 5th floor-plans have not been approved or permit issued at this time for completion of this work.
FIR07-00480 INSP-Alarm Testing6/21/20076/22/20076/22/2007 11:19:54 AMAFAIL
Horns failed to produce the required temporal pattern per NFPA 72, strobes and the duct detector functioned properly.
BLD07-00893 FIRE-Final Inspection6/21/20076/22/20076/22/2007 10:45:02 AMAPASS
Life safety inspection passed, noted contractor to repair existing emergency light at the hallway adjacent to the remodel.
FIR07-00063 FIR-Aging Inspection6/22/20076/22/20076/22/2007 10:05:21 AM DONE
Work in progress