FIR07-00528
| INSP-Sprinkler Rough-in | 6/22/2007 | 6/22/2007 | 6/26/2007 1:08:27 PM | P | CANC |
|
|
This is a duplicate inspection.
|
FIR07-00378
| INSP-Final Inspection | 6/21/2007 | 6/22/2007 | 6/22/2007 2:58:27 PM | P | PASS |
|
|
permit finaled
|
BLD05-03359
| FIRE-Final Inspection | 6/21/2007 | 6/22/2007 | 6/22/2007 12:34:47 PM | A | PART |
|
|
A temporary occupamcy was given with dave hannimans permission. The items that need to be completed are the prep booth. Its interlocks and electrical wiring within 5'/3' needs to be addressed when installed. A written notice was given to the building contractor stating the prep booth is not to be used for its intended purpose or for storage. The air outlets are to be plugged. The intelocks on the paint booth operated per IFC chapter 15 and is approved for used as far as my signoff.
|
FIR07-00426
| INSP-Sprinkler Rough-in | 6/21/2007 | 6/22/2007 | 6/22/2007 11:07:41 AM | A | PASS |
|
|
Sprinkler piping is ok to cover
|
FIR07-00496
| INSP-Sprinkler Rough-in | 6/21/2007 | 6/22/2007 | 6/22/2007 11:05:23 AM | A | PASS |
|
|
Sprinkler piping is ok to cover
|
FIR07-00523
| INSP-Final Inspection | 6/21/2007 | 6/22/2007 | 6/22/2007 10:59:17 AM | A | PASS |
|
|
The hood suppression system operated correctly. The air balance is at .025 in the negative and is ok. Two hood are installed with separate manual activation. I found that the hood have been connected to the fire alarm panel prior to having approved drawings. I notified Mike Timmerman. Bar Green is going to install an "eye brow" on the hood since vertical and horizontal distances exceed what is allowed per IMC chapter 507. This will be verified at the building final.
|
FIR07-00492
| INSP-Alarm Testing | 6/21/2007 | 6/22/2007 | 6/21/2007 1:01:39 PM | A | CANC |
|
|
randy; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang Inspection cancelled from web by: Patricia Smith
|