FIR11-00219
| INSP-Alarm Testing | 6/16/2011 | 6/17/2011 | | A | |
|
|
Phone #: ###-#### >> Inspection requested via web by Robert Gobler
|
FIR11-00212
| INSP-Sprinkler Rough-in/Hydro | 6/20/2011 | 6/22/2011 | 6/23/2011 12:44:27 PM | A | DONE |
|
|
Reference site inspection notes per T. Frost completed 6/22.
|
FIR11-00283
| INSP-Final Inspection | 6/21/2011 | 6/22/2011 | 6/22/2011 4:20:59 PM | P | PART |
|
|
Need access above drop ceiling or tiles removed to complete inspection. Spacing and locations of relocated heads appears adequate.
|
FIR06-00798
| FIR-Aging Inspection | 6/22/2011 | 6/22/2011 | 6/22/2011 3:41:55 PM | | FAIL |
|
|
No call for insp.
|
FIR11-00131
| INSP-Final Inspection | 6/21/2011 | 6/22/2011 | 6/22/2011 3:39:26 PM | P | PART |
|
|
See review note items # 5, 29 and 35 including one overspaced strobe, one MP to be relocated, provide map at the panel, need as-built plans reflecting the deletion of duct smoke detectors and removal of one non-required WP strobe, elevator test pending, one notification appliance repaired while on site. Walkthrough completed.
|
BLD11-00037
| FIRE-Final Inspection | 6/21/2011 | 6/22/2011 | 6/22/2011 3:33:10 PM | P | NR |
|
|
Final pending project related FIR permit.
|
BLD11-00880
| FIRE-Final Inspection | 6/22/2011 | 6/22/2011 | 6/22/2011 3:32:26 PM | P | PASS |
|
|
Fire life safety inspection completed satisfactory.
|
FIR10-00541
| INSP-Final Inspection | 6/21/2011 | 6/22/2011 | 6/22/2011 3:31:02 PM | A | PASS |
|
|
Fire alarm permit finaled.
|
FIR11-00190
| INSP-Final Inspection | 6/20/2011 | 6/22/2011 | 6/22/2011 3:30:17 PM | A | PASS |
|
|
Fire sprinkler permit finaled.
|
FIR07-00515
| FIR-Aging Inspection | 6/22/2011 | 6/22/2011 | 6/22/2011 12:31:17 PM | | DONE |
|
|
|
FIR07-00315
| FIR-Aging Inspection | 6/22/2011 | 6/22/2011 | 6/22/2011 12:29:57 PM | | DONE |
|
|
|
FIR05-00238
| FIR-Aging Inspection | 6/22/2011 | 6/22/2011 | 6/22/2011 12:29:29 PM | | DEFR |
|
|
New elevator work in progress.
|
FIR11-00287
| INSP-Final Inspection | 6/21/2011 | 6/22/2011 | 6/22/2011 12:20:25 PM | A | PASS |
|
|
Overhead fire sprinkler work passed both rough-in and final inspections. Permit finaled.
|
BLD04-02149
| FIRE-Final Inspection | 6/21/2011 | 6/22/2011 | 6/22/2011 10:59:04 AM | A | FAIL |
|
|
Modifications to the building fire alarm system will be necessary due to remodel work- (missing notification at the new employee work/break room).
|
BLD06-00018
| FIRE-Final Inspection | 6/21/2011 | 6/22/2011 | 6/22/2011 10:56:02 AM | A | PASS |
|
|
Fire life safety inspection passed.
|
BLD11-01191
| FIRE-Final Inspection | 6/17/2011 | 6/22/2011 | 6/22/2011 10:54:46 AM | A | FAIL |
|
|
Need to remove manual thumbturn at the main entry/exit door and provide keyed lock as discussed.
|
BLD11-01241
| FIRE-Final Inspection | 6/21/2011 | 6/22/2011 | 6/22/2011 10:53:01 AM | A | FAIL |
|
|
Correction items include; repair non-functional door at the NW excersise room, post occupant load signs as discussed, fire extinguishers are overdue annual inspection.
|
FIR11-00286
| INSP-Final Inspection | 6/21/2011 | 6/22/2011 | 6/22/2011 12:00:00 AM | A | PASS |
|
|
Sprinklers had been lowered.
|
FIR11-00159
| INSP-Sprinkler Rough-in | 6/21/2011 | 6/22/2011 | 6/22/2011 12:00:00 AM | A | FAIL |
|
|
Performed partial inspection on the second floor. Inspected sales permitter. Did not inspect rooom on the outside sales area. Did not inspect the middle of the sales. Prints are marked in red for sprinklers that were inspected. Inspection, failed. There were over spaced and missing sprinklers. The prints are marked accordingly.
|
FIR11-00025
| INSP-Final Inspection | 6/22/2011 | 6/22/2011 | | P | |
|
|
Troy phone #: ###-####
|