BLD11-00824
| FIRE-Final Inspection | 6/22/2012 | 6/22/2012 | 6/22/2012 2:53:07 PM | P | PASS |
|
|
Fire life safety inspection completed acceptable.
|
FIR12-00264
| INSP-Sprinkler Rough-in | 6/22/2012 | 6/22/2012 | 6/22/2012 2:47:58 PM | P | PART |
|
|
UG fire supply line including the IBR are approved for bury. Need to provide seismic clearance at the floor slab when poured.
|
FIR12-00233
| INSP-Final Inspection | 6/20/2012 | 6/22/2012 | 6/22/2012 1:45:57 PM | A | PASS |
|
|
Scope of fire alarm work passed functional testing. Permit finaled.
|
BLD10-02928
| FIRE-Final Inspection | 6/21/2012 | 6/22/2012 | 6/22/2012 1:44:57 PM | A | PASS |
|
|
C/N items finished. Life safety passed.
|
FIR11-00483
| INSP-Final Inspection | 6/22/2012 | 6/22/2012 | 6/22/2012 1:44:05 PM | P | NR |
|
|
Final pending project related fire alarm permit work.
|
FIR12-00271
| INSP-Sprinkler Rough-in/Hydro | 6/22/2012 | 6/22/2012 | 6/22/2012 1:43:17 PM | P | PEND |
|
|
Phone #: ###-#### >> Inspection requested via web by Mark Scharfen * Final pending project related permit work
|
FIR11-00567
| INSP-Final Inspection | 6/22/2012 | 6/22/2012 | 6/22/2012 1:39:36 PM | P | NR |
|
|
Johnathan or ###-#### Morgan Phone #: ###-#### Noted items include communication error at the panel, missing approved plans and review comments on site, butterfly valve at the forward flow does not need supervision, post signage at the door to the riser/FACP room, provide record of pre-testing.
|