FIR07-00757
| FIR-Aging Inspection | 6/22/2015 | 6/22/2015 | 6/23/2015 7:01:43 AM | | NH |
|
|
Contractor is out of business
|
FIR15-00308
| INSP-Final Inspection | 6/22/2015 | 6/22/2015 | 6/22/2015 2:52:39 PM | P | FAIL |
|
|
Need one head relocated or plugged now that the temp wall has been removed.
|
BLD15-01100
| FIRE-Final Inspection | 6/21/2015 | 6/22/2015 | 6/22/2015 1:58:46 PM | A | FAIL |
|
|
Life safety will be ok to final when the project related fire sprinkler permit is finaled
|
FIR14-00770
| INSP-Sprinkler Rough-in | 6/22/2015 | 6/22/2015 | 6/22/2015 1:44:25 PM | P | PASS |
|
|
Tenting and rough-in inspection passed. Piping can be covered. I noted a pin hole leak on a fitting that will need to be repaired prior to a hydro test.
|
FIR14-00783
| INSP-Sprinkler Rough-in/Hydro | 6/22/2015 | 6/22/2015 | 6/22/2015 1:42:54 PM | P | PASS |
|
|
Underground hydro from the backflow at the tank to the inside riser passed.
|
FIR11-00195
| INSP-Final Inspection | 6/22/2015 | 6/22/2015 | 6/22/2015 10:27:46 AM | P | PASS |
|
|
Permit finaled
|
FIR15-00415
| INSP-Sprinkler Rough-in | 6/19/2015 | 6/22/2015 | 6/22/2015 10:26:55 AM | P | PASS |
|
|
Overhead rough in inspection passed. Piping can be covered.
|
FIR15-00415
| INSP-Sprinkler Rough-in/Hydro | 6/19/2015 | 6/22/2015 | 6/22/2015 9:01:21 AM | P | FAIL |
|
|
Overhead hydro inspection failed due to puddles on the floor and I will need the pendant heads cut in prior to a hydro test.
|
FIR11-00096
| INSP-Final Inspection | 6/22/2015 | 6/22/2015 | 6/22/2015 8:25:14 AM | P | CANC |
|
|
I set up wrong inspection number
|
FIR15-00216
| INSP-Sprinkler Rough-in | 6/19/2015 | 6/22/2015 | 6/22/2015 8:23:36 AM | A | PASS |
|
|
Underground supply line cover passed
|
FIR15-00219
| INSP-Sprinkler Rough-in | 6/19/2015 | 6/22/2015 | 6/22/2015 8:22:37 AM | A | PASS |
|
|
Underground supply line cover passed.
|