ELE00-03717 Final6/22/20166/22/20166/23/2016 7:41:45 AMPFAIL
Kristy Phone #: ###-####
Enforce 2000 code as per when permit pulled.
110.3- Devices shall be wired a per manufacturers instructions. Open ground receptacle to right as you walk into bed area.
314.20- Where boxes are recessed more than 1/4" in back splast shall have extension ring installed.
GFCI under jetted tub ok, fan over shower GFCI protected at breaker. Need to check 2000 code on wall sconce 48" above tub rim not damp location rated. As per Daryl Degrange if sconce above tub ok if GFCI protected.
ELE16-01973 Electrical Rough-In6/22/20166/22/20166/22/2016 2:02:22 PMPPASS
Phone #: ###-#### Inspection requested via web by Tim Dunlop
2nd to last to west end misc lighting for warehouse. Listing confirmed. rough in ok cover
ELE16-01730 Final6/21/20166/22/20166/22/2016 1:22:55 PMPPASS
Phone #: ###-#### Inspection requested via web by Brandon Winters
Final ok
ELE16-01838 Electrical Rough-In6/22/20166/22/20166/22/2016 12:47:41 PMPPASS
headquarters level 2 stack one ceiling rough in. areas not previously ready Phone #: ###-#### Inspection requested via web by Brandon Robinson
As noted and marked on contractor print ceiling rough in ok cover
ELE16-00329 Electrical Rough-In6/21/20166/22/20166/22/2016 11:16:00 AMAPASS
Partial Final ; Ceiling
Late am if posible please Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Partial final not ready. 1st floor grid complete, transformers done, GFCI in place. As noted rough in ok cover
ELE16-01262 Final6/21/20166/22/20166/22/2016 10:33:13 AMAPASS
Keith// please call 30 min. prior Phone #: ###-#### Final ok
ELE15-02641 Electrical Rough-In6/21/20166/22/20166/22/2016 10:02:33 AMAPASS
5th Floor Ceiling Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Rooms 501, 502, 503, 504 drop lids rough in ok cover
ELE16-01746 Electrical Rough-In6/21/20166/22/20166/22/2016 9:25:39 AMAPASS
walls Phone #: ###-#### Inspection requested via web by Bryan McLaughlin
Walls and hardlids rough in ok cover
ELE16-01908 Rough-In Permanent Service6/21/20166/22/20166/22/2016 8:54:17 AMAPASS
Home is not lived in but homeowner said they would be there by 8:00am. I should be there by about then also so you can see the water pipe ground. Phone #: ###-#### Inspection requested via web by Craig Korell
Service changing from overhead to underground withsub panel in basement. New dryer circuit, range gas. p/s u/g n ok