Inspections for the day of: Wednesday, June 22, 2016.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJames Ady
TitleELE-INSPECTOR
Phone #914-4683
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE12-00654 ELE-Aging Inspection6/22/20166/22/20166/23/2016 12:30:32 PM DONE
Contractor out of buisness. Other ELE has been issued for project
ELE09-02259 ELE-Aging Inspection6/22/20166/22/20166/23/2016 12:21:24 PM DONE
Still under construction
ELE16-01927 Rough-In Permanent Service6/21/20166/22/20166/22/2016 1:52:33 PMPPASS
Phone #: ###-#### Inspection requested via web by Emmet Bushman Rough in ok to cover. p/s u/g n ok
ELE16-01955 Electrical Rough-In6/22/20166/22/20166/22/2016 1:30:48 PMPPASS
Cal-ground work/trench Phone #: ###-#### Trench from house to detached garage ok to cover
ELE15-03896 Final6/22/20166/22/20166/22/2016 1:17:17 PMPPASS
We need a final inspection please. We will have people on site until afternoon. Thank you Ryan Phone #: ###-#### Inspection requested via web by Thomas Jenkins Final ok
ELE16-01541 Final6/22/20166/22/20166/22/2016 12:54:29 PMPFAIL
Phone #: ###-#### Inspection requested via web by Eric Schroeder 406.5 Recepticles shall be securly mounted. Down wire mold. 334.15 b. NM cable shall be protected from physical damage. Under stairs
ELE16-01394 Final6/21/20166/22/20166/22/2016 11:49:30 AMAFAIL
Phone #: ###-#### Inspection requested via web by Jonathan Poot 210.8 A 1. Bathroom recepticles shall be GFCI protected. Stool and shower wall receps
ELE16-01959 Rough-In Permanent Service6/22/20166/22/20166/22/2016 11:28:35 AMAPASS
Phone #: ###-#### Inspection requested via web by daniel bibikov Rough in ok to cover. p/s o/h n ok
ELE16-01847 Final6/21/20166/22/20166/22/2016 10:27:01 AMAPASS
Alan// insp. for 2nd floor bedroom Phone #: ###-#### Final ok
ELE16-01969 Electrical Rough-In6/21/20166/22/20166/22/2016 10:00:56 AMAFAIL
Please call ahead for access - Zach Phone #: ###-#### 334.30 Securing NM cable within 12" of a box and every 4 1/2ft. 300.4 Wire throu bored holes less than 1 1/4in shall be protected. 300.4 D Cable ran parralel to framing shall be supported 1 1/4in from outside edge of framing. Discussed arc fault protection in bedrooms and tamper resistant outlets.
ELE16-00701 Electrical Rough-In6/21/20166/22/20166/22/2016 9:04:00 AMAPASS
Kevin Phone #: ###-#### Equipotential Bonding of hot tub only. Ok to cover