NAF15-00041
| INSP-Sprinkler Rough-in | 6/21/2016 | 6/22/2016 | 6/22/2016 2:19:07 PM | P | PASS |
|
|
Remainder of UDG OK to cover. Observed thrust blocks being poured.
|
NAF15-00039
| INSP-Sprinkler Rough-in/Hydro | 6/21/2016 | 6/22/2016 | 6/22/2016 2:18:27 PM | P | PASS |
|
|
Hydro static test completed satisfactory. Only flush remains.
|
NAF15-00038
| INSP-Sprinkler Rough-in/Hydro | 6/21/2016 | 6/22/2016 | 6/22/2016 2:18:05 PM | P | PASS |
|
|
Hydro static test completed satisfactory. Only flush remains.
|
NAF15-00038
| INSP-Supply line flush | 6/21/2016 | 6/22/2016 | 6/22/2016 1:17:20 PM | P | CANC |
|
|
Flush after hydro Phone #: ###-#### >> Inspection requested via web by Sam Ball Inspection cancelled from web by: Sam Ball
|
NAF15-00039
| INSP-Supply line flush | 6/21/2016 | 6/22/2016 | 6/22/2016 1:16:45 PM | P | CANC |
|
|
Flush after hydro Phone #: ###-#### >> Inspection requested via web by Sam Ball Inspection cancelled from web by: Sam Ball
|
FIR16-00185
| INSP-Final Inspection | 6/21/2016 | 6/22/2016 | 6/22/2016 10:34:21 AM | A | FAIL |
|
|
The smoke detectors and strobes on 2nd floor verified "OK". Duct detectors did not shut down fan. Following items needed: - Updated map of devices at panel - Junction box cover by relays in mech room - Retest of duct detectors to verify fan shut down
|
FIR16-00374
| INSP-Final Inspection | 6/21/2016 | 6/22/2016 | 6/22/2016 9:30:33 AM | A | PASS |
|
|
Scope of work complete. Permit Finaled.
|
BLD15-04544
| FIRE-Conference | 6/22/2016 | 6/22/2016 | 6/22/2016 12:00:00 AM | A | DONE |
|
|
Fire Sprinkler Permit is not linked to BLD. Ensure FIR16-00084 is signed off before finaling
|
GCB15-00001
| FIRE-Final Inspection | 6/22/2016 | 6/22/2016 | 6/22/2016 12:00:00 AM | A | PASS |
|
|
Life Safety Pass.
|