Inspections for the day of: Friday, June 22, 2018.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE13-03567 ELE-Aging Inspection6/22/20186/22/20186/22/2018 3:32:18 PM PASS
Finaled
ELE13-03567 Final6/22/20186/22/20186/22/2018 3:27:31 PMPPASS
Final ok
ELE18-01789 Final6/22/20186/22/20186/22/2018 3:26:01 PMPCANC
Don Phone #: ###-####
Needed permanent service inspection.
ELE18-01789 Permanent Service6/22/20186/22/20186/22/2018 3:25:41 PMPPASS
Don Phone #: ###-####
Service changed from underground to overhead. 2 breaker spaces open and need closed, will check Monday to confirm done. Called contact, no answer, mail box full unable to leave message. p/s o/h n ok
ELE18-00352 Final6/20/20186/22/20186/22/2018 3:02:04 PMAFAIL
Phone #: ###-#### Inspection requested via web by Ryan Wilson
Label main disconnect for west meter pack, secure house panel cover with all screws, All garages no access to receptacles, AFCI will not hold in 102 bed, all front outdoor receptacles shall have GFCI protection, 101 locked no access, 205 shall have a receptacle adjacent to 2nd basin in main bathroom, 205 no access to 1 bed due to door stacked blocking opening, 203 bed receptacle blocked by barn door, 202 barn door not in to check access to receptacles, 201 is staged blocking access to misc receptacles, 201 has art work over panel, no access to roof to check RTUs.
ELE17-01337 Final6/21/20186/22/20186/22/2018 12:36:25 PMAPART
Partial final, LVL 1. Phone #: ###-#### Inspection requested via web by Clint Tate Meeting rm, board rm, prefunction rm, Buffet wall, kitchen storage rms, west restrooms, meeting rm offices, employee lounge walls, server rm, work area rms, employee lounge bathroom, house keeping, linen rm, general managers office, reception area, ice rm, fitness rm, guest laundry. Areas listed above OK.
Still to complete- TV wall to fir out near reception area, guest laundry dryer receptacles, laundry equipment not ready, front vestibule door power to terminate, arc flash labels, employee lounge door power whips above grid, Kitchen panel doors will not close completely, kitchen refer GFCI device shall be below 6'7", 1 refer not gFCI protected, Kitchen ice maker not complete, Kitchen dishwasher disconnect not readily accessible lock out to be installed, seal electrical penetrations in all coolers and freezers, buffet warming pads not done listing OK, bar area not ready, floor receptacles through out not complete, pool and equipment not complete, HVAC for meeting rm not done, misc landscape not done,
Unable to sign TCO until revised TCO list is apprived from city.
ELE18-01207 Electrical Rough-In6/19/20186/22/20186/22/2018 10:55:44 AMAPASS
Contact is Dan Reichert - ceiling inspection Phone #: ###-#### Inspection requested via web by Scott Campbell
Grid rough in ok cover
ELE18-02098 Electrical Rough-In6/21/20186/22/20186/22/2018 10:55:09 AMAPASS
Ceiling Cover. Danny is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen
Grid rough in ok cover
ELE17-04065 Electrical Rough-In6/21/20186/22/20186/22/2018 10:20:55 AMAFAIL
Ceiling Cover. Danny is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen
330.30- MC shall be supported independant of grid. All luminaires shall be secured to structure basement. Call contact he stated he wanted to reschedule for monday anyway. Will recall when ready.
ELE17-02862 Electrical Rough-In6/22/20186/22/20186/22/2018 10:06:39 AMAPASS
Units 404 , 408 ,Hallway , storage ,comm rm and re inspect 405 , 406 Phone #: ###-#### Inspection requested via web by Tom Betty
Informed next trip will be turned down for make up not totally rolled in boxes subject to damage, stapling on edge, installation not in a neat workman like manner.
Rooms noted rough in ok cover
ELE18-02296 Electrical Rough-In6/21/20186/22/20186/22/2018 9:13:30 AMAPASS
Marcelo is the site contact. Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Walls and hard lids rough in ok cover
ELE17-04065 Electrical Rough-In6/21/20186/22/20186/21/2018 2:28:53 PMACANC
Ceiling cover. Danny is the contact Phone #: ###-#### >> Inspection requested via web by Buster Bowen Inspection cancelled from web by: Buster Bowen