Inspections for the day of: Friday, June 22, 2018.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR18-00432 INSP-Final Inspection6/21/20186/22/20186/22/2018 4:02:30 PMPPART
Partial final inspection for commercial hood fire suppression system complete, operational test has been completed, FIR permit for hood suppression system will remain in issued status until mechanical permit is issued for hood and is in the finaled status.

Dave Phone #: ###-####
FIR18-00431 INSP-Final Inspection6/21/20186/22/20186/22/2018 4:02:15 PMPPART
Partial final inspection for commercial hood fire suppression system complete, operational test has been completed, FIR permit for hood suppression system will remain in issued status until mechanical permit is issued for hood and is in the finaled status.

Dave Phone #: ###-####
FIR17-00471 INSP-Final Inspection6/21/20186/22/20186/22/2018 4:00:00 PMPPART
Inspection complete for room notification on levels 2 through 5. Fire sprinkler tampers and flow switches complete for levels 1 through 5, point description for standpipe control valves in riser room and level 2 roof top hose valve will be changed to discussed discription. Hood suppression monitoring is complete. Level 1 notification and common area notification and elevator recall to be tested at a later date. Monitoring needs to be verified prior to fire alarm permit being finaled.

Travis Phone #: ###-####
BLD17-04518 FIRE-Final Inspection6/22/20186/22/20186/22/2018 1:16:28 PMPPASS
No fire sprinklers, no fire alarms, fire extinguisher is in place with a current inspection tag. Final life fire safety inspection complete.

Phone #: ###-#### Inspection requested via web by Andrew Clark
FIR18-00487 INSP-Final Inspection6/22/20186/22/20186/22/2018 12:55:57 PMPPASS
Rough to cover inspection overhead fire sprinkler piping in area of work complete, approved for cover. Reliable fusible link heads with the 401 escutcheons will need to be changed to quick response heads before final inspection, head change will be verified at final inspection.

Rick- please call 30 mins ahead Phone #: ###-####
FIR18-00027 INSP-Supply line flush6/22/20186/22/20186/22/2018 11:55:51 AMPDONE
Undergorund main line flush complete for both buildings.

Phone #: ###-#### Inspection requested via web by Christophe Wilson
FIR18-00027 INSP-Sprinkler Rough-in/Hydro6/22/20186/22/20186/22/2018 11:55:18 AMADONE
Hydrostatic test witnessed for both underground main supplies, no pressure loss observed at conractor provided gauges.
FIR18-00421 INSP-Final Inspection6/21/20186/22/20186/22/2018 11:17:08 AMPCANC
Phone #: ###-#### >> Inspection requested via web by Sam Ball Inspection cancelled from web by: Sam Ball
FIR18-00316 INSP-Final Inspection6/21/20186/22/20186/22/2018 11:13:57 AMPCANC
Phone #: ###-#### >> Inspection requested via web by Sam Ball Inspection cancelled from web by: Sam Ball
BLD17-00665 FIRE-Final Inspection6/21/20186/22/20186/22/2018 11:08:26 AMPPASS
Final life fire safety inspection for scope of work complete.

Mark-please call 30 mins before Phone #: ###-####
BLD18-01554 FIRE-Final Inspection6/21/20186/22/20186/22/2018 10:41:12 AMAPASS
No fire sprinklers, no fire alarms, fire extinguisher is in place with a current inspection tag. Final life fire safety inspection complete.

Steve Phone #: ###-####
FIR18-00459 INSP-Sprinkler Rough-in6/21/20186/22/20186/22/2018 9:43:11 AMAPART
Rough to cover inspection for overhead fire sprinkler piping on level 2 canopies complete, approved for cover.

Tom Phone #: ###-####
FIR17-00586 INSP-Final Inspection6/21/20186/22/20186/22/2018 9:17:05 AMAPASS
Final fire sprinkler inspection for area of work complete.

Phone #: ###-#### Inspection requested via web by Stan Beus