Inspections for the day of: Friday, June 22, 2018.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Reynolds
TitleMEC INSPECTOR
Phone #208-803-2395
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC18-02493 Final6/18/20186/22/20186/22/2018 4:02:51 PMPPASS
Please call Karen 30 min prior to arrival Phone #: ###-#### Inspection requested via web by Andrea Grigsby- A/C coil co ok
MEC18-02257 Rough-in6/22/20186/22/20186/22/2018 3:40:46 PMPPART
cover - call mark Phone #: ###-#### Inspection requested via web by Brandon Sorensen- some ceiling grid is not installed yet where a return grille will be located. need to see return in ceiling before full R/I- ceiling ok for cover where grid is installed
MEC18-02596 Final6/19/20186/22/20186/22/2018 2:36:42 PMPFAIL
CALL (HOMEOWNER) CHARLOTTE @ # LISTED WHEN EN ROUTE FOR FINAL INSPECTION. PREFERS AROUND 2 P.M. Phone #: ###-#### Inspection requested via web by SOPHIA FLEMING- need to seal lineset penetration
MEC17-05719 Final6/22/20186/22/20186/22/2018 2:07:04 PMPFAIL
Margeaux should be home, you might call before coming just to make sure, her number is. ###-####. Thanks Phone #: ###-#### Inspection requested via web by Steve Canfield- drip legs on gas line ok- light in attic ok- need to finish taping lineset insulation completely- need to see certification on duct blast from Beeline and u can send it to my email jreynolds@cityofboise.org
MEC18-02884 Final6/21/20186/22/20186/22/2018 2:03:15 PMPCANC
Please call John to ensure install is complete. Thank you! ###-#### Phone #: ###-#### >> Inspection requested via web by Rick Borg Inspection cancelled from web by: Rick Borg
MEC18-02883 Final6/21/20186/22/20186/22/2018 1:27:20 PMPNH
Please call John to ensure install is complete. ###-####. Thank you! Phone #: ###-#### Inspection requested via web by Rick Borg
- homeowner not home reschedule
MEC18-02740 Final6/19/20186/22/20186/22/2018 1:14:54 PMPNR
Field super: Chad Robertson
requesting a phone call from inspector before heading to inspect. Phone #: ###-#### Inspection requested via web by Lisa Whitney
MEC18-02915 Final6/21/20186/22/20186/22/2018 12:49:19 PMPPASS
INSTALLER JAROD ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt- furnace ac coil co ok
MEC18-01928 Final6/21/20186/22/20186/22/2018 12:05:13 PMAFAIL
Phone #: ###-#### Inspection requested via web by Debbie Marino- No Man J. on site
MEC18-00206 Final6/22/20186/22/20186/22/2018 11:50:26 AMPPART
Contact Name: Jason Davidson Phone #: ###-#### Inspection requested via web by RM Mechanical- dryer vents ok- pool equipment room need to see ductless spilt finished- dehumid equipment condensate leaking- condensate on two ductless splits in laundry room need finished - all condensates on outside of building need terminated with an elbow down- will check roof on final inspection
MIS18-00239 MEC-Conference6/21/20186/22/20186/22/2018 10:43:16 AMAFAIL
a sper Jack R-work w/o permits
mechanical work is being done with out permits- left notice on front door stop work order
MEC18-00270 Final6/21/20186/22/20186/22/2018 10:13:55 AMAPASS
Final inspection ; Contact Todd 20 minutes prior. Thank you Phone #: ###-#### Inspection requested via web by Kim Adams- final ok- card signed
MEC18-02001 Rough-in6/15/20186/22/20186/22/2018 9:38:27 AMAPASS
CAROL ###-#### PLEASE CALL WITH ETA Phone #: ###-#### Inspection requested via web by Mike Almanza- fireplace upstairs R/I ok- fireplace downstairs R/I ok- will want to see co installed at final
MEC18-02577 Final6/20/20186/22/20186/22/2018 9:15:36 AMAPASS
Please contact Jasper for access. Please allow us 30 minutes lead time to meet on site. Phone #: ###-#### Inspection requested via web by Ted Dumont- RTU change out final ok
MEC18-02826 Final6/21/20186/22/20186/22/2018 8:44:36 AMAPASS
Russel- house is open Phone #: ###-####- A/C breaker size ok- seal tight for power ok- lineset penetration sealed ok- furnace ac coil co ok
MEC18-02926 Final6/22/20186/22/20186/22/2018 8:10:57 AMAFAIL
Inspection requested via web by Floyd Floyd Peek- need to secure grilles to ceiling grid- strap up new flex ducting in back office and return in the west open space