Inspections for the day of: Monday, June 22, 2020.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE20-02038 Temporary Service6/22/20206/22/20206/22/2020 2:25:57 PMPFAIL
Phone #: ###-#### Inspection requested via web by Alan Lusk No pole found on this lot. all lots surrounding 2271 labelled, 2 lots to the east have energized temp services in place. Recall when one is set.
ELE20-01310 Final6/22/20206/22/20206/22/2020 2:05:29 PMPPASS
Call for access Phone #: ###-#### Inspection requested via web by John VanZandt Final ok
ELE20-02017 Final6/22/20206/22/20206/22/2020 1:40:09 PMPPASS
Buddy *screened* Phone #: ###-#### Final ok
ELE20-02017 Electrical Rough-In6/22/20206/22/20206/22/2020 1:24:22 PMPPASS
Buddy *screened* Phone #: ###-#### Security door level 2 Rough in ok cover.
ELE20-00898 Electrical Rough-In6/22/20206/22/20206/22/2020 12:56:16 PMPPASS
Aaron Phone #: ###-#### Garage not dry sheeted at time of inspection. If wiring not rated for damp location gets wet it will need to be replaced. 358.6- Outdoor EMT feeding garage on outside of house shall have outdoor rated couplings and connectors.
Rough in of garage and bed wall rough in ok cover.
ELE20-01645 Electrical Rough-In6/19/20206/22/20206/22/2020 9:59:52 AMAPASS
Partial Wall Rough In - Please contact Bruce when onsite for exact locations

###-####

Thank you ; have a great day!

Phone #: ###-#### Inspection requested via web by JENNY EMEL Large conference room 630 sq. ft. 3 floor receptacles required. Walls complete rough in ok cover
ELE20-01892 Electrical Rough-In6/19/20206/22/20206/22/2020 8:55:48 AMAPASS
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Access has been provided for perimeter soffit boxes. Walls complete rough in ok cover