Inspections for the day of: Monday, June 23, 2003.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR00-00422 FIR-Aging Inspection6/23/20036/23/20036/23/2003 12:00:00 AM FAIL
There are two other FIR permits attached to this permit. Joe Tawney had made an entry approving the fire alarm upgrade on one of the permits. All three permits are for basically the same scope of work. I spoke to John Hatten with HP and he was going to look for documentation that Joe had signed off the entire project which it appears that he has. 6/23/2003 11:40:06 AM
FIR03-00133 INSP-Supply line flush6/20/20036/23/20036/23/2003 12:00:00 AMACANC
Debest will call when the thrust blocks are ready for inspection. Due to high water table pipe will be buried as it is installed and pictures will be taken and shown to the inspector before sign off 6/23/2003 2:25:25 PM
FIR02-00459 INSP-Conference6/20/20036/23/20036/23/2003 12:00:00 AMAPART
supply line hydro is ok. Rough-in inspection for areas C and D are ok except for some minor problems that have been noted on the approved plans 6/23/2003 10:33:46 AM
FIR03-00176 INSP-Sprinkler Rough-in/Hydro6/23/20036/23/20036/23/2003 12:00:00 AMAPART
started the 24 hour air test on the dry system. Started at 11:00am with 44 lbs
FIR00-00422 INSP-Final Inspection6/23/20036/23/20036/23/2003 12:00:00 AMPPASS
Per John Hatten the NFPA 72 have been signed by Joe Tawney
FIR00-00704 INSP-Final Inspection6/23/20036/23/20036/23/2003 12:00:00 AMPPASS
Per John Hatten the NFPA 72 have been signed by Joe Tawney
FIR01-00017 INSP-Final Inspection6/23/20036/23/20036/23/2003 12:00:00 AMPPASS
Per John Hatten the NFPA 72 have been signed by Joe Tawney
FIR03-00176 INSP-Sprinkler Rough-in/Hydro6/23/20036/23/20036/23/2003 12:00:00 AMPFAIL
hydro test failed due to leaking fitting on the wet system 6/23/2003 3:31:45 PM
FIR03-00256 INSP-Conference6/23/20036/23/20036/23/2003 12:00:00 AMPPART
mike ; Phone #: ###-#### rough-in inspection is ok 6/23/2003 4:17:08 PM
FIR00-00419 INSP-Sprinkler Rough-in/Hydro6/20/20036/23/20036/23/2003 12:00:00 AMPFAIL
KERRY- ###-#### Provide new friction loss for the different anti-freeze backflow preventer. Provide asbuilts with all changes. Signs for all valves and all other close out items as listed on the review notes. Provide verification that the new front canopies do not require protection since they appear to have combustibles inside. Pendants are still too close to supply registers. Provide clearance for operation of the PIV. Provide hydro test certificates 6/23/2003 2:08:21 PM