FIR00-00422
| FIR-Aging Inspection | 6/23/2003 | 6/23/2003 | 6/23/2003 12:00:00 AM | | FAIL |
|
|
There are two other FIR permits attached to this permit. Joe Tawney had made an entry approving the fire alarm upgrade on one of the permits. All three permits are for basically the same scope of work. I spoke to John Hatten with HP and he was going to look for documentation that Joe had signed off the entire project which it appears that he has. 6/23/2003 11:40:06 AM
|
FIR03-00133
| INSP-Supply line flush | 6/20/2003 | 6/23/2003 | 6/23/2003 12:00:00 AM | A | CANC |
|
|
Debest will call when the thrust blocks are ready for inspection. Due to high water table pipe will be buried as it is installed and pictures will be taken and shown to the inspector before sign off 6/23/2003 2:25:25 PM
|
FIR02-00459
| INSP-Conference | 6/20/2003 | 6/23/2003 | 6/23/2003 12:00:00 AM | A | PART |
|
|
supply line hydro is ok. Rough-in inspection for areas C and D are ok except for some minor problems that have been noted on the approved plans 6/23/2003 10:33:46 AM
|
FIR03-00176
| INSP-Sprinkler Rough-in/Hydro | 6/23/2003 | 6/23/2003 | 6/23/2003 12:00:00 AM | A | PART |
|
|
started the 24 hour air test on the dry system. Started at 11:00am with 44 lbs
|
FIR00-00422
| INSP-Final Inspection | 6/23/2003 | 6/23/2003 | 6/23/2003 12:00:00 AM | P | PASS |
|
|
Per John Hatten the NFPA 72 have been signed by Joe Tawney
|
FIR00-00704
| INSP-Final Inspection | 6/23/2003 | 6/23/2003 | 6/23/2003 12:00:00 AM | P | PASS |
|
|
Per John Hatten the NFPA 72 have been signed by Joe Tawney
|
FIR01-00017
| INSP-Final Inspection | 6/23/2003 | 6/23/2003 | 6/23/2003 12:00:00 AM | P | PASS |
|
|
Per John Hatten the NFPA 72 have been signed by Joe Tawney
|
FIR03-00176
| INSP-Sprinkler Rough-in/Hydro | 6/23/2003 | 6/23/2003 | 6/23/2003 12:00:00 AM | P | FAIL |
|
|
hydro test failed due to leaking fitting on the wet system 6/23/2003 3:31:45 PM
|
FIR03-00256
| INSP-Conference | 6/23/2003 | 6/23/2003 | 6/23/2003 12:00:00 AM | P | PART |
|
|
mike ; Phone #: ###-#### rough-in inspection is ok 6/23/2003 4:17:08 PM
|
FIR00-00419
| INSP-Sprinkler Rough-in/Hydro | 6/20/2003 | 6/23/2003 | 6/23/2003 12:00:00 AM | P | FAIL |
|
|
KERRY- ###-#### Provide new friction loss for the different anti-freeze backflow preventer. Provide asbuilts with all changes. Signs for all valves and all other close out items as listed on the review notes. Provide verification that the new front canopies do not require protection since they appear to have combustibles inside. Pendants are still too close to supply registers. Provide clearance for operation of the PIV. Provide hydro test certificates 6/23/2003 2:08:21 PM
|