ELE06-02316
| Electrical Rough-In | 6/23/2006 | 6/23/2006 | 6/23/2006 4:52:02 PM | P | PASS |
|
|
u/g ok to cover, will need to call for ps and sign feed ltr
|
ELE06-01641
| Final | 6/23/2006 | 6/23/2006 | 6/23/2006 4:31:21 PM | P | PASS |
|
|
need final inspection on new electrical to partitions. thank you.; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH ok to final
|
ELE06-01173
| Electrical Rough-In | 6/23/2006 | 6/23/2006 | 6/23/2006 4:17:28 PM | P | PASS |
|
|
underground inspection Internet Inspection Request from: Rowdy Monroe u/g around inside of bldg and elect room ok to cover
|
ELE06-02355
| Electrical Rough-In | 6/23/2006 | 6/23/2006 | 6/23/2006 3:31:13 PM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Daryl DeGrange u/g only ok to cover
|
ELE06-01407
| Final | 6/23/2006 | 6/23/2006 | 6/23/2006 2:40:10 PM | P | PASS |
|
|
tim - reinsp; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ok to final
|
ELE06-02351
| Electrical Rough-In | 6/23/2006 | 6/23/2006 | 6/23/2006 2:25:12 PM | P | FAIL |
|
|
Phone #: ###-#### Please call 30 min prior to going. Internet Inspection Request from: Rita DeYoung called, left messages, left corr notice, nec 330.30(B) mc cable shall be secured within 12" of boxes, 300.4(D) edge of cable shall be 1 1/4" from edge of framing members (includes raceways), 362.30(A) ent shall be fastened at 3' intervals,Note: no wiring in valley of studs
|
ELE06-02311
| Electrical Rough-In | 6/21/2006 | 6/23/2006 | 6/23/2006 1:47:58 PM | P | PASS |
|
|
underground inspection, please contact Miles, thank you; Phone #: ###-#### Internet Inspection Request from: Wendy Waters gec only ok to cover
|
ELE06-01332
| Final | 6/22/2006 | 6/23/2006 | 6/23/2006 1:07:20 PM | P | PASS |
|
|
steve; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corr made, ok to final
|
ELE06-01191
| Final | 6/22/2006 | 6/23/2006 | 6/23/2006 12:01:15 PM | A | PASS |
|
|
shelly; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ok to final, corr made
|
ELE06-02337
| Final | 6/22/2006 | 6/23/2006 | 6/23/2006 10:44:13 AM | A | PASS |
|
|
Work performed by Tom Wonacott.; Phone #: ###-#### Internet Inspection Request from: Matt Santacruz ok to final
|
ELE06-01237
| Final | 6/22/2006 | 6/23/2006 | 6/23/2006 10:17:17 AM | A | NH |
|
|
Phone #: ###-#### Internet Inspection Request from: Therrin Robertson called said to recall
|
ELE06-01407
| Final | 6/22/2006 | 6/23/2006 | 6/23/2006 9:47:24 AM | A | FAIL |
|
|
tim; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called left corr notice, 9637 side, nec 210.11(C)(3) bathroom recpt shall have no other outlets on branch circuit( front door trips bath gfci)
|
ELE06-01042
| Final | 6/22/2006 | 6/23/2006 | 6/23/2006 9:26:17 AM | A | PASS |
|
|
marilynn; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ok to final
|
ELE06-02305
| Temporary Service | 6/21/2006 | 6/23/2006 | 6/23/2006 8:58:16 AM | A | FAIL |
|
|
Jim; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt called, left corr notice, nec 408.36(FG) plug in type overcurrent devices that are backfed shall be secured in place by an additional fastener, 408.4 circuit directory shall be complete,BCC job id sticker shall be posted
|
ELE06-02332
| Rough-In Permanent Service | 6/22/2006 | 6/23/2006 | 6/23/2006 8:21:26 AM | A | PASS |
|
|
Shelly; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt ric ok, p/s u/g n ok
|