Inspections for the day of: Tuesday, June 23, 2009.
Number of inspections: 21
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE08-01532 ELE-Aging Inspection6/23/20096/23/20097/1/2009 3:24:35 PM DONE
no activity, suc
ELE09-00603 Final6/22/20096/23/20096/23/2009 4:07:14 PMPCANC
ron Phone #: ###-#### called, no access, contractor will set up inspection when card available, after sign core and shall card, no esc this project
ELE09-00359 Final6/22/20096/23/20096/23/2009 4:04:50 PMPPART
ron Phone #: ###-#### looked at roof-top unit, building locked, called contractor, will call when accesible, can sign card when available
ELE09-00427 Final6/19/20096/23/20096/23/2009 3:44:36 PMPCANC
Travis Phone #: ###-#### wrong type inspection, see conference, no esc this project
ELE09-01092 Electrical Rough-In6/22/20096/23/20096/23/2009 3:09:51 PMPPASS
Please contact Patrick Crisler @ ###-#### at the Catholic Diocese and he will let you in to the area we performed work and show you the area where we worked. Thank you. Phone #: ###-#### Internet Inspection Request from: Clint Tate ric ok, no esc this project
ELE09-01097 Final6/23/20096/23/20096/23/2009 2:35:14 PMPFAIL
Phone #: ###-#### Internet Inspection Request from: bill shipley called, left correction notice, NEC 312.5 all conductors entering enclosures shall have abrasion protection, 250.8 grounding conductors shall be terminated, 406.8 receptacles shall be listed weather resistant,590.6 shall provide gfci protection for receptacles, BCC shall post job id sticker no esc this project
ELE09-01100 Permanent Service6/23/20096/23/20096/23/2009 1:40:23 PMPFAIL
Calvin Phone #: ###-#### called, left correction notice, NEC 110.22 disconnects shall be labelled for its purpose, 250.8(A) grounding lug shall be connected with machine screws or at least 2 threads, 250.92(B)(4) shall use bond bushings, locknuts or other listed device at service disconnect, 110.12(A) unused openings shall be closed, 3230.72(C)each occupent shall have access to service disconnects, 225.37 shall identify all service disconnects and meters, 230.23 conductors shall have sufficient ampacity to carry the current for the load, no esc this project
ELE09-00530 Final6/22/20096/23/20096/23/2009 12:50:48 PMAPASS
Garage code is 02430 Phone #: ###-#### Internet Inspection Request from: Joe Thomas ok to final
ELE09-00352 Final6/22/20096/23/20096/23/2009 12:04:36 PMAPASS
Garage code is 02430 Phone #: ###-#### Internet Inspection Request from: Joe Thomas ok to final
ELE09-00527 Final6/22/20096/23/20096/23/2009 11:44:14 AMAPASS
Garage code is 02430 Phone #: ###-#### Internet Inspection Request from: Joe Thomas ok to final
ELE09-00353 Final6/22/20096/23/20096/23/2009 11:36:56 AMAPASS
Garage code is 02430 Phone #: ###-#### Internet Inspection Request from: Joe Thomas ok to final
ELE09-01093 Electrical Rough-In6/22/20096/23/20096/23/2009 10:15:23 AMAPASS
sprinkler timeclock is ready for inspection Phone #: ###-#### Internet Inspection Request from: gary batten ric ok, no esc this project
ELE09-01093 Final6/23/20096/23/20096/23/2009 10:14:47 AMAPASS
sprinkler timeclock is ready for inspection Phone #: ###-#### Internet Inspection Request from: gary batten ok to final, no esc this project
ELE09-01093 Permanent Service6/23/20096/23/20096/23/2009 10:13:27 AMAPASS
sprinkler timeclock is ready for inspection Phone #: ###-#### Internet Inspection Request from: gary batten p/s u/g n ok, no esc this project
ELE09-01087 Final6/22/20096/23/20096/23/2009 10:11:35 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Lloyd Looney called contractor, ok to final
ELE08-00409 Electrical Rough-In6/22/20096/23/20096/23/2009 9:50:33 AMAPART
Joe Phone #: ###-#### ok to cover ceilings anop
ELE08-00409 Final6/23/20096/23/20096/23/2009 9:24:24 AMAPART
Joe Phone #: ###-#### ok to final beauty salon anop, signed occupancy card
ELE09-01085 Electrical Rough-In6/22/20096/23/20096/23/2009 9:18:33 AMAPASS
bill Phone #: ###-#### ric ok, no esc this project
ELE08-03276 Final6/22/20096/23/20096/23/2009 8:51:11 AMAPASS
neil Phone #: ###-#### ok to final, signed occupancy card
ELE09-00737 Final6/22/20096/23/20096/23/2009 8:13:07 AMAPASS
ed Phone #: ###-#### ok to final, signed structural card
ELE09-00638 Final6/22/20096/23/20096/23/2009 7:37:49 AMAPASS
jim Phone #: ###-#### corrections made for ri, devices installed, ok to final, no esc this project