BLD09-00420
| FIRE-Final Inspection | 6/23/2009 | 6/23/2009 | 6/23/2009 6:23:18 PM | P | FAIL |
|
|
Need to repair the new exit sign on backup power source, repair the existing EM light, provide approved hardware at the restroom door, remove the deadbolt at the back exit door per approved plan notes-see annotations.
|
BLD09-00008
| FIRE-Final Inspection | 6/23/2009 | 6/23/2009 | 6/23/2009 6:20:59 PM | P | PASS |
|
|
Life safety is satisfactory pending the removal of the manual thumbturn deadbolt at the second exit door to be done prior to structural final for verification at that time.
|
FIR08-00449
| INSP-Sprinkler Rough-in/Hydro | 6/22/2009 | 6/23/2009 | 6/23/2009 6:18:29 PM | A | PART |
|
|
Rough-in approved for cover at the sheetrock ceilings.
|
FIR08-00448
| INSP-Sprinkler Rough-in/Hydro | 6/22/2009 | 6/23/2009 | 6/23/2009 6:16:52 PM | A | PART |
|
|
Overhead fire sprinkler modifications are good for ceiling cover.
|
FIR08-00446
| INSP-Sprinkler Rough-in/Hydro | 6/22/2009 | 6/23/2009 | 6/23/2009 6:15:32 PM | A | PART |
|
|
Overhead rough-in okayed for cover, one upright head removed while on site, be aware of possible light fixture obstructions due to junction box locations and pendent heads.
|
FIR08-00447
| INSP-Sprinkler Rough-in/Hydro | 6/22/2009 | 6/23/2009 | 6/23/2009 12:10:45 PM | A | FAIL |
|
|
Coverage is obstructed at one room, two pendent heads exceed min. spacing, one upright head needs removed.
|
FIR09-00264
| INSP-Sprinkler Rough-in/Hydro | 6/22/2009 | 6/23/2009 | 6/23/2009 11:17:15 AM | A | PART |
|
|
Concluded satisfactory 24 hr. pneumatic testing with allowable pressure loss of 1/2 psi.
|
FIR07-00350
| INSP-Final Inspection | 6/23/2009 | 6/23/2009 | 6/23/2009 11:09:17 AM | A | PASS |
|
|
Fire alarm permit okayed for final status, see activity notes.
|
FIR09-00238
| INSP-Alarm Testing | 6/22/2009 | 6/23/2009 | 6/23/2009 11:07:43 AM | A | NR |
|
|
Scheduled by a contractor via Hello! on 6/22/2009 at 8:24:58 PM. Contact: ###-####. Pending project related fire alarm permit work.
|
FIR09-00238
| INSP-Conference | 6/22/2009 | 6/23/2009 | 6/23/2009 11:06:49 AM | A | DONE |
|
|
Regarding items needed for completion and permit final.
|