Inspections for the day of: Tuesday, June 23, 2009.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD09-00420 FIRE-Final Inspection6/23/20096/23/20096/23/2009 6:23:18 PMPFAIL
Need to repair the new exit sign on backup power source, repair the existing EM light, provide approved hardware at the restroom door, remove the deadbolt at the back exit door per approved plan notes-see annotations.
BLD09-00008 FIRE-Final Inspection6/23/20096/23/20096/23/2009 6:20:59 PMPPASS
Life safety is satisfactory pending the removal of the manual thumbturn deadbolt at the second exit door to be done prior to structural final for verification at that time.
FIR08-00449 INSP-Sprinkler Rough-in/Hydro6/22/20096/23/20096/23/2009 6:18:29 PMAPART
Rough-in approved for cover at the sheetrock ceilings.
FIR08-00448 INSP-Sprinkler Rough-in/Hydro6/22/20096/23/20096/23/2009 6:16:52 PMAPART
Overhead fire sprinkler modifications are good for ceiling cover.
FIR08-00446 INSP-Sprinkler Rough-in/Hydro6/22/20096/23/20096/23/2009 6:15:32 PMAPART
Overhead rough-in okayed for cover, one upright head removed while on site, be aware of possible light fixture obstructions due to junction box locations and pendent heads.
FIR08-00447 INSP-Sprinkler Rough-in/Hydro6/22/20096/23/20096/23/2009 12:10:45 PMAFAIL
Coverage is obstructed at one room, two pendent heads exceed min. spacing, one upright head needs removed.
FIR09-00264 INSP-Sprinkler Rough-in/Hydro6/22/20096/23/20096/23/2009 11:17:15 AMAPART
Concluded satisfactory 24 hr. pneumatic testing with allowable pressure loss of 1/2 psi.
FIR07-00350 INSP-Final Inspection6/23/20096/23/20096/23/2009 11:09:17 AMAPASS
Fire alarm permit okayed for final status, see activity notes.
FIR09-00238 INSP-Alarm Testing6/22/20096/23/20096/23/2009 11:07:43 AMANR
Scheduled by a contractor via Hello! on 6/22/2009 at 8:24:58 PM. Contact: ###-####. Pending project related fire alarm permit work.
FIR09-00238 INSP-Conference6/22/20096/23/20096/23/2009 11:06:49 AMADONE
Regarding items needed for completion and permit final.