Inspections for the day of: Tuesday, June 23, 2009.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD09-00858 BLD-Conference6/23/20096/23/20096/23/2009 4:14:32 PMPPASS
I discussed new door hardware issues with the tenant.
BLD08-01304 FIRE-Final Inspection6/22/20096/23/20096/23/2009 4:13:45 PMPFAIL
Exit signs need to be installed as noted on the plans for the east most exit doors or other arrangements need to be made with the plan reviewer. Also exit discharge lighting is required for the south facing exits as shown on the plans.
FIR09-00247 INSP-Final Inspection6/23/20096/23/20096/23/2009 4:10:19 PMPFAIL
The plans do not reflect the additional sprinklers heads in the compressor room that have been added to the the anti-freeze system. Per my discussion with Tim Frost these changes need to be resubmitted due to the adjacent remote hydraulic area being effected by a non self closing door. Also two 45 fittings have been added at the base of the riser which are not shown on the plans. The backflow preventor needs to be certified and the forward flush performed.
BLD08-02274 FIRE-Final Inspection6/22/20096/23/20096/23/2009 4:09:47 PMAFAIL
The city approved plans and notes were not on site for an inspection. Jim is going to track them down from the pool people.
FIR08-00830 INSP-Sprinkler Rough-in/Hydro6/23/20096/23/20096/23/2009 4:07:13 PMPPASS
The insulation has been installed on the second floor and is satifactory for cover.
FIR09-00338 INSP-Alarm Testing6/22/20096/23/20096/23/2009 1:17:37 PMPPASS
Permit finaled. The phone lines had to be enabled as I waited.
FIR09-00082 FIR-Aging Inspection6/23/20096/23/20096/23/2009 8:44:01 AM NR
work is in progress